2-10
PQM Power Quality Meter
GE Power Management
2.2 ELECTRICAL
2 INSTALLATION
2
Three-wire systems with voltages 600 V (L-L) or less can be directly connected to the PQM without VTs. Select
the
S2 SYSTEM SETUP \ CURRENT/VOLTAGE CONFIGURATION \ VT WIRING: 3 WIRE DELTA DIRECT
setpoint.
The PQM voltage inputs should be directly connected using HRC fuses rated at 2 amps to ensure adequate
interrupting capacity.
Figure 2–8: WIRING DIAGRAM 3-WIRE DIRECT (NO VTs)