7-18
PQM Power Quality Meter
GE Power Management
7.3 MODBUS MEMORY MAP
7 MODBUS COMMUNICATIONS
7
CLOCK
0230
Time - Hours/Minutes
---
---
---
F22
N/A
0231
Time - Seconds
---
---
---
F23
N/A
0232
Time - Month/Day
---
---
---
F24
N/A
0233
Time Year
---
---
---
F25
N/A
0234
Reserved
to
↓
↓
↓
↓
↓
↓
023F
Reserved
CURRENT
0240
Phase A Current
---
---
A
F1
N/A
0241
Phase B Current
---
---
A
F1
N/A
0242
Phase C Current
---
---
A
F1
N/A
0243
Average Current
---
---
A
F1
N/A
0244
Neutral Current
---
---
A
F1
N/A
0245
Current Unbalance
---
---
0.1 x%
F1
N/A
0246
Phase A Current - Minimum
A
F1
N/A
0247
Phase B Current - Minimum
A
F1
N/A
0248
Phase C Current - Minimum
A
F1
N/A
0249
Neutral Current - Minimum
A
F1
N/A
024A
Current Unbalance - Minimum
0.1 x%
F1
N/A
024B
Phase A Current - Maximum
A
F1
N/A
024C
Phase B Current - Maximum
A
F1
N/A
024D
Phase C Current - Maximum
A
F1
N/A
024E
Neutral Current - Maximum
A
F1
N/A
024F
Current Unbalance - Maximum
0.1 x%
F1
N/A
0250
Time - Hour/Minutes of Phase A Curr. Min
---
---
---
F22
N/A
0251
Time - Seconds of Phase A Current Min
---
---
---
F23
N/A
0252
Date - Month/Day of Phase A Current Min
---
---
---
F24
N/A
0253
Date - Year of Phase A Current Min
---
---
---
F25
N/A
0254
Time - Hour/Minutes of Phase B Curr. Min
---
---
---
F22
N/A
0255
Time - Seconds of Phase B Current Min
---
---
---
F23
N/A
0256
Date - Month/Day of Phase B Current Min
---
---
---
F24
N/A
0257
Date - Year of Phase B Current Min
---
---
---
F25
N/A
0258
Time - Hour/Minutes of Phase C Curr. Min
---
---
---
F22
N/A
0259
Time - Seconds of Phase C Current Min
---
---
---
F23
N/A
025A
Date - Month/Day of Phase C Current Min
---
---
---
F24
N/A
025B
Date - Year of Phase C Current Min
---
---
---
F25
N/A
025C
Time - Hour/Minutes of Neutral Current Min
---
---
---
F22
N/A
025D
Time - Seconds of Neutral Current Min
---
---
---
F23
N/A
025E
Date - Month/Day of Neutral Current Min
---
---
---
F24
N/A
025F
Date - Year of Neutral Current Min
---
---
---
F25
N/A
0260
Time - Hour/Minutes of Current Unbal. Min
---
---
---
F22
N/A
0261
Time - Seconds of Current Unbalance Min
---
---
---
F23
N/A
0262
Date - Month/Day of Current Unbal. Min
---
---
---
F24
N/A
0263
Date - Year of Current Unbalance Min
---
---
---
F25
N/A
0264
Time - Hour/Minutes of Phase A Curr. Max
---
---
---
F22
N/A
Table 7–10: PQM MEMORY MAP (Sheet 4 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Summary of Contents for Power Quality Meter Series
Page 2: ......
Page 4: ......
Page 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Page 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Page 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Page 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Page 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Page 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Page 281: ...GE Power Management PQM Power Quality Meter NOTES ...