GE Power Management
PQM Power Quality Meter
7-61
7 MODBUS COMMUNICATIONS
7.3 MODBUS MEMORY MAP
7
F107
con’t
Analog Input Alt Alarm
0040
Data Log 1
0080
Data Log 2
0100
Negative Real Power Demand alarm
0200
Negative Reactive Power Demand Alarm
0400
Pulse Input 2 Alarm
0800
Pulse Input 3 Alarm
1000
Pulse Input 4 Alarm
2000
Totalized Pulse Input Alarm
4000
Time Alarm
8000
F108
INTERNAL FAULT ERROR CODE
FFFF
ADC Reference Out of Range
0001
HC705 Processor Not Responding
0002
Switch Input Circuit Fault
0004
HC705 MOR Byte is Not Programmed
0008
Not Used
0010
Not Used
0020
Not Used
0040
Not Used
0080
Not Used
0100
Not Used
0200
Not Used
0400
Not Used
0800
Not Used
1000
Not Used
2000
Not Used
4000
Not Used
8000
F109
GENERAL STATUS
FFFF
Alarm Present
0001
Clock Not Set
0002
Clock Drifting
0004
Data Log 1 Running
0008
Data Log 2 Running
0010
Not Used
0020
Not Used
0040
Not Used
0080
Not Used
0100
Not Used
0200
Not Used
0400
Not Used
0800
Not Used
1000
Not Used
2000
Not Used
4000
Not Used
8000
F110
DATA LOGGER NUMBERS
FFFF
Log 1
0001
Log 2
0002
Table 7–11: MEMORY MAP DATA FORMATS (Sheet 13 of 16)
CODE
DESCRIPTION
BITMASK
F110
con’t
Not Used
0004
Not Used
0008
Not Used
0010
Not Used
0020
Not Used
0040
Not Used
0080
Not Used
0100
Not Used
0200
Not Used
0400
Not Used
0800
Not Used
1000
Not Used
2000
Not Used
4000
Not Used
8000
F111
EVENT RECORD SWITCHES AND RELAY STATUS
FFFF
Alarm Relay
0001
Auxiliary Relay 1
0002
Auxiliary Relay 2
0004
Auxiliary Relay 3
0008
Not Used
0010
Not Used
0020
Not Used
0040
Not Used
0080
Switch A
0100
Switch B
0200
Switch C
0400
Switch D
0800
Not Used
1000
Not Used
2000
Not Used
4000
Not Used
8000
F112
EVENT RECORDER EVENT ENABLE FLAGS 4
FFFF
Power On
0001
Power Off
0002
Alarm / Control Reset
0004
Setpoint Access Enable
0008
Not Used
0010
Not Used
0020
Not Used
0040
Not Used
0080
Not Used
0100
Not Used
0200
Not Used
0400
Not Used
0800
Not Used
1000
Not Used
2000
Not Used
4000
Table 7–11: MEMORY MAP DATA FORMATS (Sheet 14 of 16)
CODE
DESCRIPTION
BITMASK
Summary of Contents for Power Quality Meter Series
Page 2: ......
Page 4: ......
Page 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Page 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Page 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Page 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Page 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Page 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Page 281: ...GE Power Management PQM Power Quality Meter NOTES ...