GE Power Management
PQM Power Quality Meter
7-63
7 MODBUS COMMUNICATIONS
7.3 MODBUS MEMORY MAP
7
7.3.5 ANALOG OUTPUT PARAMETER RANGE
Table 7–12: ANALOG OUTPUT PARAMETER RANGE FOR SERIAL PORTS (Sheet 1 of 2)
NO.
ANALOG OUT PARAMETER
RANGE
STEP
UNITS/
SCALE
DEFAULT
0
Not Used
0
0
---
0
1
Phase A Current
0 to 150
1
%
0
2
Phase B Current
0 to 150
1
%
0
3
Phase C Current
0 to 150
1
%
0
4
Neutral Current
0 to 150
1
%
0
5
Average Phase Current
0 to 150
1
%
0
6
Current Unbalance
0 to 1000
1
0.1 x%
0
7
Voltage Van
0 to 200
1
%
0
8
Voltage Vbn
0 to 200
1
%
0
9
Voltage Vcn
0 to 200
1
%
0
10
Voltage Vab
0 to 200
1
%
0
11
Voltage Vbc
0 to 200
1
%
0
12
Voltage Vca
0 to 200
1
%
0
13
Average Phase Voltage
0 to 200
1
%
0
14
Average Line Voltage
0 to 200
1
%
0
15
Voltage Unbalance
0 to 1000
1
0.1 x%
0
16
Frequency
0 to 7500
1
0.01 xHz
0
17
*3 Phase PF
–99 to +99
1
0.01 xPF
0
18
3 Phase kW
–32500 to +32500
1
kW
0
19
3 Phase kvar
–32500 to +32500
1
kvar
0
20
3 Phase kVA
0 to 65400
1
kVA
0
21
3 Phase MW
–32500 to +32500
1
0.1 xMW
0
22
3 Phase Mvar
–32500 to +32500
1
0.1 xMvar
0
23
3 Phase MVA
0 to 65400
1
0.1 xMVA
0
24
*Phase A PF
–99 to +99
1
0.01 xPF
0
25
Phase A kW
–32500 to +32500
1
kW
0
26
Phase A kvar
–32500 to +32500
1
kvar
0
27
Phase A kVA
0 to 65400
1
kVA
0
28
*Phase B PF
–99 to +99
1
0.01 xPF
0
29
Phase B kW
–32500 to +32500
1
kW
0
30
Phase B kvar
–32500 to +32500
1
kvar
0
31
Phase B kVA
0 to 65400
1
kVA
0
32
*Phase C PF
–99 to +99
1
0.01 xPF
0
33
Phase C kW
–32500 to +32500
1
kW
0
34
Phase C kvar
–32500 to +32500
1
kvar
0
35
Phase C kVA
0 to 65400
1
kVA
0
36
3 Phase +kWh Used
0 to 65400
1
kWh
0
37
3 Phase +kvarh Used
0 to 65400
1
kvarh
0
*
Due to the fact that –0 and +0 both exist for power factor, the value stored in the PQM serial register is the
opposite of the value shown on the display.
Example: If the range 0.23 lead (–0.23) to 0.35 lag (+0.35) is required, –77 (–100+23)and +65 (100–35) must
be sent.
Summary of Contents for Power Quality Meter Series
Page 2: ......
Page 4: ......
Page 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Page 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Page 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Page 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Page 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Page 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Page 281: ...GE Power Management PQM Power Quality Meter NOTES ...