7-32
PQM Power Quality Meter
GE Power Management
7.3 MODBUS MEMORY MAP
7 MODBUS COMMUNICATIONS
7
MESSAGE
BUFFER
continued
04DC
Message Buffer characters 9 and 10
---
---
ASCII
F10
N/A
04DD
Message Buffer characters 11 and 12
---
---
ASCII
F10
N/A
04DE
Message Buffer characters 13 and 14
---
---
ASCII
F10
N/A
04DF
Message Buffer characters 15 and 16
---
---
ASCII
F10
N/A
04E0
Message Buffer characters 17 and 18
---
---
ASCII
F10
N/A
04E1
Message Buffer characters 19 and 20
---
---
ASCII
F10
N/A
04E2
Message Buffer characters 21 and 22
---
---
ASCII
F10
N/A
04E3
Message Buffer characters 23 and 24
---
---
ASCII
F10
N/A
04E4
Message Buffer characters 25 and 26
---
---
ASCII
F10
N/A
04E5
Message Buffer characters 27 and 28
---
---
ASCII
F10
N/A
04E6
Message Buffer characters 29 and 30
---
---
ASCII
F10
N/A
04E7
Message Buffer characters 31 and 32
---
---
ASCII
F10
N/A
04E8
Message Buffer characters 33 and 34
---
---
ASCII
F10
N/A
04E9
Message Buffer characters 35 and 36
---
---
ASCII
F10
N/A
04EA
Message Buffer characters 37 and 38
---
---
ASCII
F10
N/A
04EB
Message Buffer characters 39 and 40
---
---
ASCII
F10
N/A
04EC
Reserved
to
↓
↓
↓
↓
↓
↓
04F7
Reserved
HIGH SPEED
SAMPLES
FOR
HARMONIC
SPECTRUM
04F8
High Speed Sampling Parameter
---
---
---
F26
N/A
04F9
High Speed Sampling Scale Factor (high)
---
---
A or V x 10000
F3
N/A
04FA
High Speed Sampling Scale Factor (low)
---
---
A or V x 10000
F3
N/A
04FB
Freq. of High Speed Sampling Waveform
---
---
0.01 xHz
F1
N/A
04FC
Time - Hours/Minutes of Last Sampling
---
---
---
F22
N/A
04FD
Time - Seconds of Last Sampling
---
---
---
F23
N/A
04FE
Date - Month/Day of Last Sampling
---
---
---
F24
N/A
04FF
Date - Year of Last Sampling
---
---
---
F25
N/A
0500
High Speed Sample Buffer 1
---
---
ADC counts
F2
N/A
0501
High Speed Sample Buffer 2
---
---
ADC counts
F2
N/A
0502
High Speed Sample Buffer 3
---
---
ADC counts
F2
N/A
0503
High Speed Sample Buffer 4
---
---
ADC counts
F2
N/A
to
↓
↓
↓
↓
↓
↓
05FD
High Speed Sample Buffer 254
---
---
ADC counts
F2
N/A
05FE
High Speed Sample Buffer 255
---
---
ADC counts
F2
N/A
05FF
High Speed Sample Buffer 256
---
---
ADC counts
F2
N/A
0600
Reserved
to
↓
↓
↓
↓
↓
↓
061F
Reserved
WAVEFORM
CAPTURE
HEADER
0620
Time - Hours/Minutes of Last Capture
---
---
---
F22
N/A
0621
Time - Seconds of Last Capture
---
---
---
F23
N/A
0622
Date - Month/Day of Last Capture
---
---
---
F24
N/A
0623
Date - Year of Last Capture
---
---
---
F25
N/A
0624
Frequency of Last Capture
---
---
0.01 x Hz
F1
N/A
0625
Reserved
Table 7–10: PQM MEMORY MAP (Sheet 18 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Summary of Contents for Power Quality Meter Series
Page 2: ......
Page 4: ......
Page 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Page 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Page 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Page 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Page 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Page 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Page 281: ...GE Power Management PQM Power Quality Meter NOTES ...