5–14
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
S2 PROTECTION
CHAPTER 5: SETPOINTS
The trip time for the NEMA compatible overcurrent curves are shown below.
K+E 11”
×
17” format for the NEMA-compatible time overcurrent curves are available from
factory upon request.
Table 5–2: Nema Compatible Overload Curve Trip Times (in Seconds)
Overload
level
Curve
Class 10
Class 15
Class 20
Class 30
1.05
3349
5024
6698
10047
1.10
1635
2452
3269
4904
1.20
780
1170
1560
2340
1.30
497
746
995
1492
1.40
358
536
715
1073
1.50
275
412
549
824
1.75
166
250
333
499
2.00
114
172
229
343
2.25
84
127
169
253
2.50
65
98
131
196
2.75
52
78
105
157
3.00
43
64
86
129
3.50
30
46
61
91
4.00
23
34
46
67
4.50
17.8
27
36
53
5.00
14.3
21
29
43
5.50
11.7
17.6
23
35
6.00
9.8
14.7
19.6
29.4
6.50
8.3
12.4
16.6
24.9
7.00
7.1
10.7
14.3
21.4
7.50
6.2
9.3
12.4
18.6
8.00
5.4
8.1
10.9
16.3
NOTE
Summary of Contents for MM3
Page 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Page 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Page 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Page 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...