5–42
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
S7 TESTING
CHAPTER 5: SETPOINTS
The switch inputs simulation settings are programmed as follows:
•
SIMULATION
: Enter “ON” to switch from actual switch inputs to the programmed
simulation status of each switch input. While simulation is on the actual switch input
status will be overridden by the simulated status of each input. Set to “OFF” after
simulation is complete. As a safeguard, simulation will automatically turn off if:
• power to the MM3 Motor Manager 3 is turned off and on
• the time programmed in
SIMULATION ENABLED FOR
has elapsed since simulation
was first enabled
When switch inputs simulation is turned on the
SWITCH IN SIMULATION HAS BEEN
ENABLED
flash message will be displayed for 3 seconds. When switch inputs is turned off
the
SWITCH IN SIMULATION HAS BEEN DISABLED
flash message will be displayed for 3
seconds.
•
SIMULATION ENABLED FOR
: Select the length of time that simulation is enabled.
When this time has elapsed, switch inputs simulation will turn off. If “UNLIMITED” is
selected, simulated switch input status will be used until simulation is turned off via
the
SIMULATION
setpoint, via the serial port, or until control power is removed.
•
START A INPUT
and
START B INPUT
: Enter the status of these switch inputs as “OPEN”
or “CLOSED”. The functionality of these inputs remains as is with actual input
connected.
•
STOP INPUT
: Enter the status of this switch input as “OPEN” or “CLOSED”. The
functionality of this input remains as is with actual input connected.
•
CONTACTOR A STATUS INPUT
and
CONTACTOR B STATUS INPUT
: Enter the status of
these switch inputs as “OPEN” or “CLOSED”. The functionality of these inputs remains
as is with actual input connected.
•
LOCAL ISOLATOR INPUT
: Enter the status of this switch input as “OPEN” or “CLOSED”.
The functionality of this input remains as is with actual input connected.
•
INTERLOCK 1 INPUT
to
INTERLOCK 10 INPUT
: Enter the status of these switch inputs
as “OPEN” or “CLOSED”. The functionality of these inputs remains as is with actual
input connected.
5.8.7
Thermistor
Simulation
PATH: S7 TESTING
ÖØ
THERMISTOR SIMULATION
The thermistor simulation settings are programmed as follows:
•
SIMULATION
: Enter “ON” to switch from actual thermistor input to the programmed
simulation thermistor resistance value. While simulation is on the actual thermistor
input will be overridden by the simulated resistance value. Select “OFF” after
simulation is complete. As a safeguard, simulation will automatically turn off if:
• power to the MM3 Motor Manager 3 is turned off and on
] THERMISTOR
] SIMULATION
SIMULATION:
OFF
Range: ON, OFF
SIMULATION ENABLED
FOR:
15 min.
Range: 5 to 300 min. or UNLIMITED in
steps of 5
THERMISTOR
RESISTANCE: 0
Ω
Range: 0 to 30000
Ω
in steps of 1
Summary of Contents for MM3
Page 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Page 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Page 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Page 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...