CHAPTER 8: COMMUNICATIONS
MODBUS MEMORY MAP
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
8–23
44130
4129
1021
High speed phase CT
primary amps
0 to
1000
1
A
F1
0 =
NONE
44131
4130
1022
...Reserved...
...
...
...
...
...
44132
4131
1023
Ground CT type
0 to 1
1
--
F13
0 =
50:0.025
44133
4132
1024
VT primary voltage
110 to
691
1
---
F1*
691 =
OFF
44134
4133
1025
VT connection type
0 to 1
1
---
F15
0 = PHASE
(A-N)
44135
4134
1026
VT secondary voltage
110 to
240
10
V
F1
120
44136
4135
1027
Nominal frequency
50 to
60
10
Hz
F1
60
Thermistor (read/write setpoints)
44137
4136
1028
Cold resistance
1 to
300
1
0.1
×
kW
F1
1 = 0.1
kW
44138
4137
1029
Hot resistance
1 to
300
1
0.1
×
kW
F1
50 = 5.0
kW
44139
4138
102A
Thermistor trip
0 to 1
1
---
F14
0 =
DISABLE
44140
4139
102B
Thermistor alarm
0 to 1
1
---
F14
0 =
DISABLE
44141
4140
102C
...Reserved...
...
...
...
...
...
Thermistor simulation (read/write setpoints)
44142
4141
102D
Thermistor simulation
0 to 1
1
F20
0 = OFF
44143
4142
102E
Thermistor resistance
0 to
30000
1
ohms
F1
0 ohms
44144
4143
102F
Thermistor simulation
period
5 to
305
5
min.
F1**
15 min.
Fault mode (read/write setpoints)
44145
4144
1030
Internal fault trip
0 to 1
1
---
F14
1 =
ENABLE
44146
4145
1031
Serial communications
failure trip
5 to 30
5
---
F1*
30 = OFF
44147
4146
1032
Serial communications
failure alarm
5 to 30
5
---
F1*
30 = OFF
44148
4147
1033
Change command mode
on alarm
0 to 1
1
---
F14
0 =
DISABLE
44149
4148
1034
...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44152
4151
1037
...Reserved...
...
...
...
...
...
Motor protection: thermal (read/write setpoints)
44153
4152
1038
Full load current
0 to
1000
1
**
F1
†
0 = OFF
44154
4153
1039
High speed full load
current
5 to
1000
1
**
F1
100
44155
4154
103A
Overload curve number
1 to 12
1
---
F1
4
44156
4155
103B
Hot/cold curve ratio
20 to
100
1
%
F1
75
Table 8–2: Modbus Memory Map (Sheet 8 of 28)
Modicon
Address
Description
Range
Step
Units Format
Default
dec.
hex
* – Maximum setpoint value and 65535 represent OFF; ** – 1/phase current scale factor
×
A; *** – 101
represents unlimited;
† – Minimum setpoint value represents OFF; ~ – 0.1
×
A when high resolution mode is disabled;
0.01
×
A when enabled
Summary of Contents for MM3
Page 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Page 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Page 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Page 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...