CHAPTER 8: COMMUNICATIONS
MODBUS MEMORY MAP
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
8–41
Preset counters and timers (read/write setpoints)
44657
4656
1230
Preset running hours
0 to
65535
1
---
F1
0
44658
4657
1231
Preset stopped hours
0 to
65535
1
---
F1
0
44659
4658
1232
Preset number of starts -
high order
0 to
65535
1
---
F1
0
44660
4659
1233
Preset number of starts -
low order
0 to
65535
1
---
F1
0
44661
4660
1234
Preset overload trips
0 to
65535
1
---
F1
0
44662
4661
1235
Preset thermistor trips
0 to
65535
1
---
F1
0
44663
4662
1236
Preset ground fault trips
0 to
65535
1
---
F1
0
44664
4663
1237
Preset single phase trips
0 to
65535
1
---
F1
0
44665
4664
1238
Preset acceleration trips
0 to
65535
1
---
F1
0
44666
4665
1239
Preset undercurrent trips
0 to
65535
1
---
F1
0
44667
4666
123A
Preset underpower trips
0 to
65535
1
---
F1
0
44668
4667
123B
Preset stalled rotor trips
0 to
65535
1
---
F1
0
44669
4668
123C
Preset control command
trips
0 to
65535
1
---
F1
0
44670
4669
123D
Preset interlock counter
0 to
65535
1
---
F1
0
44671
4670
123E
...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44702
4701
125D
...Reserved...
...
...
...
...
...
Relays and LED simulation (read/write setpoints)
44703
4702
125E
Relays and LEDs simulation
0 to 1
1
---
F37
0 = OFF
44704
4703
125F
...Reserved...
...
...
...
...
...
Current simulation (read/write setpoints)
44705
4704
1260
Current simulation
0 to 1
1
F37
0 = OFF
44706
4705
1261
Simulated phase A current
0 to
10000
1
***
F1
0
44707
4706
1262
Simulated phase B current
0 to
10000
1
***
F1
0
44708
4707
1263
Simulated phase C current
0 to
10000
1
***
F1
0
44709
4708
1264
Simulated ground current
0 to
500.0
0.1
0.1 A
F1
0
44710
4709
1265
Simulated voltage
0 to
3000
1
V
F1
0
44711
4710
1266
Simulated power
0 to
359
1
kW
F1
0
Table 8–2: Modbus Memory Map (Sheet 26 of 28)
Modicon
Address
Description
Range
Step
Units Format
Default
dec.
hex
* – Maximum setpoint value and 65535 represent OFF; ** – 1/phase current scale factor
×
A; *** – 101
represents unlimited;
† – Minimum setpoint value represents OFF; ~ – 0.1
×
A when high resolution mode is disabled;
0.01
×
A when enabled
Summary of Contents for MM3
Page 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Page 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Page 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Page 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...