Testing
7.1
Injection Testing
7.1.1
Primary
Injection
Testing
Prior to MM3 Motor Manager 3 commissioning, complete system operation can be verified
by injecting current through the phase and ground fault CTs. To accomplish this, a current
injection test set is required.
Operation of the entire MM3 Motor Manager 3 control/protection system, except the phase
and ground fault CTs, can be checked by applying input signals to the MM3 Motor Manager
3 from a secondary injection test set as described in this chapter.
7.1.2
Secondary
Injection
Testing
The figure below shows a simple, single-phase secondary injection test circuit that can be
used to perform the tests described in this chapter. Tests should be performed to verify the
correct operation and wiring. All functions are firmware driven and this testing is required
only to verify correct firmware/hardware interaction.
The tests described in the following sections can be repeated and modified using setpoints
and current levels more closely suited to the actual installation.
Summary of Contents for MM3
Page 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Page 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Page 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Page 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...