CHAPTER 6: ACTUAL VALUES
A2 STATUS
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
6–11
speed output relay (contactor A) will energize, or the time remaining until the forward
output relay (contactor A) or the reverse output relay (contactor B) will energize.
•
RESTART INHIBIT
: This message will appear when an autotransformer start is
inhibited. The restart inhibit time is determined from the autotransformer starts per
hour setpoint.
•
EXTERNAL START
: This message will appear if the contactor closed without receiving a
start command from the MM3 Motor Manager 3. The MM3 Motor Manager 3 will close
the corresponding output relay to seal in the contactor.
•
CAUSE OF STOP
: This message will appear to indicate the cause of the current stop
condition.
•
CAUSE OF LAST STOP
: This message indicates the cause of the last stop operation.
•
EXTERNAL STOP
: This message indicates that the stop operation was caused
externally to the MM3 Motor Manager 3; that is, the contactor coil de-energized