CHAPTER 5: SETPOINTS
S1 CONFIGURATION
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
5–9
enter the resistance that the thermistor must rise above before a thermistor trip or
alarm can be cleared.
•
HOT RESISTANCE
: For a PTC thermistor, enter the resistance that the thermistor must
rise above before a thermistor trip or alarm will occur. For a NTC thermistor, enter the
resistance that the thermistor must drop below before a thermistor trip or alarm will
occur.
•
THERMISTOR TRIP
: When a thermistor is used, it can be selected for an alarm or trip or
both. Choose “ENABLE” to allow thermistor trips to occur.
•
THERMISTOR ALARM
: When a thermistor is used, it can be selected for an alarm or
trip or both. Choose “ENABLE” to allow thermistor alarms to occur.
5.2.6
Fault Mode
PATH: S1 CONFIGURATION
ÖØ
FAULT MODE
The fault mode settings are programmed as follows:
•
INTERNAL FAULT TRIP
: An internal fault during self-checking will cause an alarm.
Since operation may be erratic depending on the fault condition, it may be desirable
to trip the motor by setting this setpoint to “ENABLE”. The MM3 Motor Manager 3
continues to run the motor with an internal fault present if set to “DISABLE”.
•
SERIAL COMMS FAILURE TRIP
: If the serial communications link is used to control a
process with several motors working together, it may be desirable to shut down the
motor if communication control is lost. When no activity occurs on the
communications port for 5 to 25 seconds, it will trip if this feature is enabled.
•
SERIAL COMMS FAILURE ALARM
: Sets an alarm when the serial communication link is
interrupted.
•
CHANGE COMMAND MODE ON ALARM
: Allows the command mode to automatically
switch from AUTO to MANUAL when the
SERIAL COMMS FAILURE ALARM
is active. If the
motor was running when the alarm occurred it will be stopped and will restart based
on manual start inputs only. When serial communication is restored the MM3 Motor
Manager 3 will remain in MANUAL command mode.
5.2.7
Statistics
PATH: S1 CONFIGURATION
ÖØ
STATISTICS
] FAULT MODE
]
INTERNAL FAULT TRIP:
ENABLE
Range: Enable, Disable
SERIAL COMMS FAILURE
TRIP: OFF s
Range: 5 to 25 s or OFF in steps of 5
SERIAL COMMS FAILURE
ALARM: OFF
Range: 5 to 25 s or OFF in steps of 5
CHANGE COMMAND MODE
ON ALARM: DISABLE
Range: Enable, Disable
] STATISTICS
]
CLEAR TIMERS:
DISABLE
Range: Enable, Disable
CLEAR START/TRIP
COUNTERS: DISABLE
Range: Enable, Disable
Summary of Contents for MM3
Page 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Page 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Page 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Page 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...