CHAPTER 6: ACTUAL VALUES
A2 STATUS
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
6–9
•
DRIVE FAILED TO START
: An inverter starter has failed to complete a start sequence.
This occurs on an inverter starter when, during a start sequence, contactor A closes as
expected but contactor B fails to close.
•
DRIVE FAILED TO STOP
: An inverter starter has failed to complete its stop sequence.
This occurs on an inverter starter when contactor B fails to open during a stop
sequence.
•
INCOMPLETE START
: An autotransformer starter has failed to complete its start
sequence. This occurs on an autotransformer starter start sequence when contactor
A closes as expected but contactor B fails to close.
•
UNDERPOWER ALARM
: The power has dropped below the underpower alarm level for
the underpower alarm time delay.
•
MOTOR GREASING INTERVAL EXCEEDED
: The motor greasing interval time has been
exceeded.
•
CONTACT INSPECTION INTERVAL EXCEEDED
: The number of contactor operations
has exceeded the contactor inspection interval alarm count.
•
MAXIMUM MOTOR STOP TIME EXCEEDED
: The time that the motor has remained
stopped has exceeded the maximum motor stopped time alarm level. This can be
cleared by starting the motor.
•
ANALOG HIGH ALARM
: The analog input value has exceeded the analog input high
alarm level for the analog input high alarm time delay.
•
ANALOG LOW ALARM
: The analog input value has dropped below the analog input
low alarm level for the analog input low alarm time delay.
•
PROCESS INTERLOCK A
to
PROCESS INTERLOCK J
: An open process interlock switch
input (A through J) has been detected.
•
MOTOR A TRIP ALARM
: A duty/standby starter type motor has tripped. The cause of
the trip is displayed on the bottom line.
•
THERMAL CAPACITY ALARM
: The thermal capacity used has exceeded the alarm level.
•
UNDERVOLTAGE ALARM
: The primary voltage measurement has dropped below the
alarm level.
•
OVERVOLTAGE ALARM
: The primary voltage measurement has exceeded the alarm
level.
•
START BLOCK ALARM
: A start block is in effect.
Summary of Contents for MM3
Page 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Page 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Page 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Page 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...