5–38
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
S7 TESTING
CHAPTER 5: SETPOINTS
5.8
S7 Testing
5.8.1
Test
Configuration
PATH: S7 TESTING
Ö
TEST CONFIGURATION
The test configuration settings are programmed as follows:
•
DISPLAY CONTACTOR MONITORING
: This message enables or disabled contactor
monitoring during simulation tests and prevents open control circuit and welded
contactor alarms.
•
MONITOR DISABLED FOR
: Selects the desired length of time that monitoring will be
disabled.
•
DISABLE STATISTICS LOGGING
: This setpoint determines whether statistics are
accumulated during simulation tests (for example, number of starts, etc.).
5.8.2
Test Relays
and LEDs
PATH: S7 TESTING
ÖØ
TEST RELAYS & LEDS
To verify correct operation of output relay wiring, each output relay and status indicator
can be manually forced on or off via the keypad or serial port. Testing is only allowed if
there is no phase and ground current present, no trips are present, the
RELAYS & LEDS
SIMULATION
setpoint is ON, and setpoint access is enabled.
If the test is attempted while current is present, the setpoint will be forced to “NORMAL
MODE” and the
RELAY TEST BLOCKED - CURRENT PRESENT
flash message will be
displayed for 3 seconds.
If any trips are present, the setpoint will be forced to NORMAL MODE and the
SIMULATION
BLOCKED - TRIP PRESENT
flash message will be displayed for 3 seconds.
If testing is attempted via the serial port while phase or ground current is present, a trip is
present, or the
RELAYS & LEDS SIMULATION
setpoint is OFF, an error code will be returned.
The following values can be chosen for the
OPERATION TEST
setpoint: “NORMAL MODE”,
“CONTACTOR A ON”, “CONTACTOR B ON”, “AUX RELAY 1 ON”, “AUX RELAY 2 ON”, “ALL RELAYS
ON”, “RUNNING LED ON”, “STOPPED LED ON”, “TRIPPED LED ON”, “ALARM LED ON”, “AUTO
LED ON”, “MANUAL LED ON”, “ALL LEDS ON”.
] TEST CONFIGURATION
]
DISPLAY CONTACTOR
MONITORING: NO
Range: YES, NO
MONITORING DISABLED
FOR:
15 min.
Range: 5 to 300 minutes in steps of 5
DISABLE STATISTICS
LOGGING: NO
Range: YES, NO
] TEST RELAYS & LEDS
]
RELAYS & LEDS
SIMULATION: OFF
Range: ON, OFF
OPERATION TEST:
NORMAL MODE
Range: see below
Summary of Contents for MM3
Page 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Page 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Page 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Page 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...