CHAPTER 5: SETTINGS
TRANSDUCER INPUTS/OUTPUTS
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5-337
5
RRTD 1 ALARM PKP DELAY
— This setting specifies time delay for the alarm stage until the output can be asserted. The range
of 5 to 600 seconds differs from the existing RTD settings to correspond to the range of the RRTD unit.
RRTD 1 TRIP TEMPERATURE
— This setting specifies the temperature pickup level for the trip stage. The range of 1 to 200°C
differs from the existing RTD settings to correspond to the range of the RRTD unit.
RRTD 1 TRIP PKP DELAY
— This setting specifies time delay for the trip stage until the output can be asserted. The range of 5
to 600 seconds differs from the existing RTD settings to correspond to the range of the RRTD unit.
RRTD 1 TRIP RST DELAY
— This setting specifies the reset delay to seal-in the trip signal.
RRTD 1 TRIP VOTING
— This setting allows securing trip signal by voting with other RTDs. A value of “None” indicates that
element operates individually and no voting takes place.
A value of “Group” indicates that element is allowed to issue a trip if N – 1 of other RTDs of the same group pick up as well
(where N is the number of enabled RTDs from the group). For example, if three RTDs are assigned to the same group, there
needs to be at least one additional RTD of the same group picked up to issue a trip command.
The “Remote RTD 1” through “Remote RTD 12” values indicate that element is allowed to issue a trip if the corresponding
peer RTD is also picked up.
RRTD 1 OPEN
— This setting allows monitoring an open remote RTD sensor circuit. If this functionality is not required, then a
value of “None” disables monitoring and assertion of output operands. If set to “Alarm”, the monitor sets an alarm when a
broken sensor is detected. If set to “Block”, the monitor sets an alarm and simultaneously block remote RTD operation
when a broken sensor is detected.
If targets are enabled, a message appears on the display identifying the broken RTD. If this feature is used, it is
recommended that the alarm be programmed as latched so that intermittent RTDs are detected and corrective action can
be taken.
RRTD 1 BLOCK
— This setting is used to block remote RTD operation.
Figure 5-191: Remote RTD input protection logic
5.10.4 DCmA outputs
SETTINGS
TRANSDUCER I/O
DCMA OUTPUTS
DCMA OUTPUT H1(W8)
DCMA OUTPUT H1
DCMA OUTPUT H1
SOURCE: Off
Range: Off, any analog actual value parameter
DCMA OUTPUT H1
RANGE: –1 to 1 mA
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Summary of Contents for M60
Page 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Page 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...