5-292
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
gravitational force causes reverse rotation to subside. Starting when the load is reversing can cause damage to the
motor or pump.
5.8.7.2 Maximum starting rate (ANSI 66)
SETTINGS
CONTROL ELEMENTS
START SUPERVISION
MAXIMUM STARTING RATE
The element can be programmed to perform the classical monitoring function of Starts Per Hour. However, time interval
units specified by the
START/HR TIME INTERVAL
setting are in minutes for increased flexibility. The
STARTS/HR MAX NUMBER OF
STARTS
setting specifies the start attempt number limit during the interval. The time unit and ranges accommodate the
starting requirements of large direct-on-line motors.
The element asserts the following three FlexLogic operands:
•
The
STARTS-PER-HOUR PKP
operand indicates that the maximum permitted starting rate has been reached. When
stopped, the motor is not restarted until the lockout time elapses.
•
The
STARTS-PER-HOUR OP
operand indicates that the motor stopped when the maximum permitted starting rate was
already reached. Use this operand to inhibit the start command.
•
The
STARTS-PER-HOUR DPO
operand indicates that the maximum permitted starting rate has not been reached. When
stopped, the motor can be restarted immediately.
The element uses motor status asserted by the Thermal Model element. The thermal protection must be configured
properly in order for this function to operate.
Figure 5-163: Maximum starting rate logic
MAXIMUM STARTING
RATE (STARTS/HR)
STARTS/HR FUNCTION:
Disabled
Range: Disabled, Enabled
STARTS/HR TIME
INTERVAL: 60 min
Range: 1 to 300 minutes in steps of 1
STARTS/HR MAX NUMBER
OF STARTS: 3
Range: 1 to 16 in steps of 1
STARTS/HR BLOCK:
Off
Range: FlexLogic operand
STARTS/HR TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled
STARTS/HR EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for M60
Page 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Page 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...