2-36
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
2
LED INDICATORS
Functions:
5 device status indicators
9 event cause indicators
8 user-programmable pushbutton indicators
PUSHBUTTONS
Type:
membrane
Functions:
5 bottom Tab pushbuttons and 1 Home pushbutton for page recall
4 directional, 1 ENTER, and 1 ESCAPE pushbutton element selection
10 side pushbuttons for power system element control
RESET pushbutton
8 physical user-programmable pushbuttons, 8 graphical interface pushbuttons
INGRESS PROTECTION
IP code:
IP20 front, IP54 front with graphical front panel, IP10 back
2.5.12 Environmental
AMBIENT TEMPERATURES
Storage temperature:
–40 to 85°C
Operating temperature:
–40 to 60°C; the LCD contrast can be impaired at temperatures less than –20°C
HUMIDITY
Humidity:
operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days)
OTHER
Altitude:
2000 m (maximum)
Pollution degree:
II
Overvoltage category:
II
Ingress protection:
IP20 front, IP10 back
Noise:
0 dB
Summary of Contents for M60
Page 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Page 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...