CHAPTER 5: SETTINGS
GROUPED ELEMENTS
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5-217
5
Figure 5-116: Thermal model logic
5.7.3.4 AMP unbalance (ANSI 46)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
MOTOR
AMP UNBALANCE 1(2)
AMP UNBALANCE 1
AMP UNBAL 1
FUNCTION: Disabled
Range: Disabled, Enabled
AMP UNBAL 1 PICKUP:
0.0%
Range: 0.0 to 100.0% in steps of 0.1
AMP UNBAL 1 PICKUP
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
AMP UNBAL 1 RESET
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
AMP UNBAL 1 BLOCK:
Off
Range: FlexLogic operand
AMP UNBAL 1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled