Fail Alarm
Part 17997
Rev. 6, March 2011
10-17
Table 10-9 - Battery Voltage Fault Triggers
For explanations on the battery, see Section 2.7 on page 2-15.
10.5.2.4
Sensor Operation and Connections Fault Triggers
A sensor test is automatically performed on the first and fifteenth days of each month at
midnight, and relevant parameters are recorded in the
History;Service
file. The test can
also be forced manually (
Service;ForceSensor Test
command), but the result is not
recorded. In both cases, one of the alarm messages shown in Table 10-10 on page 10-17 is
displayed if the sensor fails the test.
Table 10-10 - Sensor Operation and Connections Fault Triggers
10.5.3 Fail Alarm Cancellation
Note: To be cancelled, an alarm condition must disappear during a period of time
exceeding the corresponding alarm delay (if existing for this condition).
To cancel a fail alarm, proceed as follows:
1.
Find and solve the problem (for help, see Section 10.5.2 on page 10-15).
Description
Priority
Alarm Set
Point
Fault Trigger Alarm Message
Low-Low battery voltage Average
Batt.Alr LL Batt. LL
Low battery voltage
Very low
Batt.Alr L
Batt. L
Description
Priority Alarm Set Point Fault Trigger Alarm Message
Replace sensor soon Average
None
SensRep Soon Replace SensSoon
Replace sensor now
Very high
SensRep Now Replace SensNOW
Cable
a
short
a.
Either one of the following cables (or connectors in the connection link): Sensor, sensor
thermistor or heating plate thermistor.
CableShort
Cable
a
open
CableOpen
Summary of Contents for Hydran 201i
Page 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Page 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Page 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Page 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Page 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 299: ......