Chapter 10 • Alarms
10-2
Rev. 6, March 2011
Part 17997
10.1
ALARM LEVELS
The Hydran 201
i
System is a microprocessor-based family of instruments with sophisti-
cated alarm features. It is equipped with three alarm levels:
•
Gas High alarm
(Hydran 201T
i
’s Alarm 1): This alarm is set at a lower gas level than
the High-High alarm. It is a caution sign and should initiate closer monitoring of the
equipment.
•
Gas High-High alarm
(H201T
i
’s Alarm 2): This alarm is set at a higher level than the
High alarm. It is a warning sign and should trigger immediate operator action according
to standard utility procedures.
•
Fail alarm of the Hydran 201i System
: This alarm includes all alarms other than the High
and High-High alarms. The fail alarm warns the operator that the Hydran 201
i
System is
not functioning properly. A fail alarm must therefore be verified and solved rapidly
because it indicates that the
monitoring
system (the Hydran 201
i
System) of the
transformer is faulty.
Note: A fail alarm does not concern the transformer.
The High and High-High alarms provide an
early warning of incipient faults
in trans-
formers or any other oil-filled electrical equipment.
10.1.1 Alarm Conditions
An alarm is triggered when an
alarm condition
is detected. Each alarm has its own set of
alarm conditions.
Gas High and High-High alarms are triggered by one or several of the following conditions:
• The
level of gases in oil
exceeds the user-defined alarm set point (250 ppm, for example).
The gas level is a composite value of the following gases: Hydrogen (H
2
), carbon
monoxide (CO), acetylene (C
2
H
2
) and ethylene (C
2
H
4
).
• The
hourly trend
(short term) of the gas level exceeds the user-defined alarm set point
(10 ppm per 24 hours, for example). The hourly trend represents the level variation of
gases in the oil during a period of time measured in hours. The hourly trend is updated
every five seconds.
• The
daily trend
(long term) of the gas level exceeds the user-defined alarm set point
(25 ppm per 30 days, for example). The daily trend represents the level variation of gases
Summary of Contents for Hydran 201i
Page 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Page 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Page 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Page 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Page 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 299: ......