March 2008
D-2
Foundation Fieldbus Communications
Configuration Utility
Setup
The following is an example setup using National Instruments
Configuration Utility v3.1.
Figure D-1 below shows the Configuration Utility with a flowmeter
on the network (GE Flow-XMT).
Figure D-1: Configuration Utility Setup Example
Note:
The following procedures assume that the device has been
placed in the OOS (out-of-service) mode before executing.
Selecting the Desired
Measurements
To set the measurement unit for each AI:
1.
Double click on the
FLOW
Transducer Block (in the tree under
GEFlow-XMT
).
2.
Select the
Others
tab and open the drop down list for the
PRIMARY_SELECTOR
and
SECONDARY_SELECTOR
(refer to
3.
Choose the unit from the list (see Figure D-2 on page D-3).
This unit will correspond to the unit that is available in the AI block
for network connection. The
PRIMARY_SELECTOR
unit will
correspond to
ANALOG_INPUT_1
and the
SECONDARY_SELECTOR
will correspond to
ANALOG_INPUT_2
.
Summary of Contents for DigitalFlow GS868
Page 7: ...Chapter 1 ...
Page 59: ...Chapter 2 ...
Page 77: ...Chapter 3 ...
Page 90: ...Chapter 4 ...
Page 104: ...Chapter 5 ...
Page 110: ...Chapter 6 ...
Page 122: ...Appendix A ...
Page 131: ...Appendix B ...
Page 132: ...Data Records Option Cards Installed B 1 Initial Setup Data B 2 ...
Page 136: ...Appendix C ...
Page 156: ...Appendix D ...