Page
25
REMOTE RESET
(Note This option may use the Linefault or KS terminal). The Line Fault or the K/S
terminal (dependant on option 127 Remote Reset Source) also doubles as the Remote
Reset input (normally found on Red-Care STUs sometimes termed as Remote Signal
Path). To use this feature the 'REMOTE RESET' option should be programmed to ON
(option 39). After an alarm the control panel will reset when 12V is applied to this
terminal.
The feature allows the use of RedCare units with Remote Reset even when a Modem
is connected. It should be noted that the triggers for the RedCare should be from the
P.A, D1 & D2 terminal.
Do not use the 12Hr or L/F terminal as they double as a
data connection for the Modem.
The Remote Reset feature may also be used to auto-reset the control panel after an
alarm. This must only be used on non BS 4737 systems when the panel is being used
for purposes other than security. The auto-reset is achieved by leaving the factory
fitted link in position and turning the 'REMOTE RESET' (option 39) ON
PA
This terminal is the Digicom output for PA (Personal Attack)and would normally be
connected to channel 2 of a communicator. The output is open collector and has a
maximum current sink of 50mA*
1
*
2
12HR
This terminal is the Digicom output for 12HR (Alarm )and would normally be connected
to channel 3. The output is open collector and has a maximum current sink of 50mA*
1
*
2
If the ProDigi or Modem are not used PA & 12Hr are programmable under the option
D3 & D4
Note:
When testing Digicom Channels via menu 65 (Test Digicom Channels)
and Digicom type Normal has been selected the display will show
1 2 3 4 with zeros under each number. In this instance 1 refers to D1
output. 2 refers to PA output (D3). 3 refers to 12Hr output (D4). 4 refers
to D2 output.
*
1
No attempt should be made to exceed the stated current and the 1 Amp
maximum current draw from the control panel must be taken into consideration.
*
2
Some Digicoms may require a 6K8 pull-up resistor fitting between this output
and 12V
GardTec
872
Wiring Connections