Heating operation
Switch the airflow AUTO, and the indoor fan motor will run according to a room temperature, as be-
low.
On the other hand, if switched in HIGH—QUIET, the indoor motor will run at a constant airflow of
HEAT operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Heating: Auto)
When the room
temperature rises
When the room
temperature drops
LOW mode
MED mode
MED+ mode
Tr - Ts ≥ -1
°C
-2
°C > Tr - Ts
Tr - Ts ≥ -1.5
°C
-1.5
°C
> Tr - Ts ≥ -2.5
°C
-2.5
°C > Tr - Ts
-1
°C
> Tr - Ts ≥ -2
°C
Cool air prevention control (heating mode)
The maximum value of the indoor fan speed is set as shown below, based on the detected tempera-
ture by the indoor heat exchanger sensor on heating mode.
•
Normal operation
42°C
Indoor heat exchanger
temperature rises
HIGH
or setting fan mode*
Cool air prevention
S-LOW
Indoor heat exchanger
temperature drops
39°C
37°C
30°C
37°C
34°C
32°C
28°C
MED+
or setting fan mode*
LOW
or setting fan mode*
*: Lower speed is selected.
13 minutes later:
42°C
Indoor heat exchanger
temperature rises
HIGH
or setting fan mode*
Indoor heat exchanger
temperature drops
39°C
37°C
30°C
37°C
34°C
32°C
28°C
MED+
or setting fan mode*
LOW
or setting fan mode*
*: Lower speed is selected.
LOW
or setting fan mode*
LOW
or setting fan mode*
3-1. Indoor fan control
- (04-53) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AGHG09KVCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 15 SR_CH01_MU001EG_04 ...
Page 40: ...2 6 Outdoor unit 01 34 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 41: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 15 SR_CH02_MU001EG_05 ...
Page 44: ......
Page 161: ...3 TROUBLESHOOTING 2022 04 13 SR_CH03_MU001EG_04 ...
Page 164: ......
Page 259: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU001EG_06 ...
Page 262: ......
Page 351: ...5 FILED WORKING 2022 04 13 SR_CH05_MU001EG_05 ...