2-26. E: 64. PFC circuit error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
6 time flash
Timer indicator
4 time flash
Economy indicator
Continuous flash
Error code
E: 64
Detective actuator
Outdoor unit
Main PCB
•
When inverter input DC voltage is higher than 415
V (14 type) or 420 V (18 type) for over 3 seconds,
the compressor stops.
•
If the same operation is repeated 5 times, the
compressor stops permanently.
Forecast of cause
External cause
Connector connection failure
Main PCB failure
Check point 1. Check external cause at indoor and outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 2. Check connection of Connector
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 3. Replace the main PCB
If check point 1 to 2 do not improve the symptom, replace the main PCB.
↓
End
2-26. E: 64. PFC circuit error (Outdoor unit)
- (03-39) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AGHG09KVCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 15 SR_CH01_MU001EG_04 ...
Page 40: ...2 6 Outdoor unit 01 34 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 41: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 15 SR_CH02_MU001EG_05 ...
Page 44: ......
Page 161: ...3 TROUBLESHOOTING 2022 04 13 SR_CH03_MU001EG_04 ...
Page 164: ......
Page 259: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU001EG_06 ...
Page 262: ......
Page 351: ...5 FILED WORKING 2022 04 13 SR_CH05_MU001EG_05 ...