1-3. Dry operation
The rotation number of the compressor shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the table below.
Zone is defined by set temperature and room temperature.
¢
Compact cassette type
•
Rotation number range of compressor
Unit: rps
– Model: AOHG14KBTA2
Model name
Outdoor temperature zone
Operating rotation number
AUXG07KVLA
AUXG09KVLA
AUXG12KVLA
X zone
50
J zone
50
Y zone
0
AUXG14KVLA
X zone
44
J zone
44
Y zone
0
– Model: AOHG18KBTA2
Model name
Outdoor temperature zone
Operating rotation number
AUXG07KVLA
AUXG09KVLA
AUXG12KVLA
X zone
50
J zone
50
Y zone
0
AUXG14KVLA
X zone
42
J zone
42
Y zone
0
•
Compressor control based on room temperature
Ts+0.5°C
Ts -1.5
°C
Ts-0.5
°C
Ts+1.5
°C
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
1-3. Dry operation
- (04-15) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AGHG09KVCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 15 SR_CH01_MU001EG_04 ...
Page 40: ...2 6 Outdoor unit 01 34 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 41: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 15 SR_CH02_MU001EG_05 ...
Page 44: ......
Page 161: ...3 TROUBLESHOOTING 2022 04 13 SR_CH03_MU001EG_04 ...
Page 164: ......
Page 259: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU001EG_06 ...
Page 262: ......
Page 351: ...5 FILED WORKING 2022 04 13 SR_CH05_MU001EG_05 ...