2-20. E: 57. Damper (Open/Close) detection limit switch error
Indicator
Indoor unit
Operation indicator
5 time flash
Timer indicator
7 time flash
Economy indicator
Continuous flash
Error code
E: 57
Detective actuator
Indoor unit main PCB
•
When limit switch were not able to detect the close
though the damper close.(Upper air flow)
•
When limit switch were not able to detect the open
though the damper open.(Upper & Lower air flow)
Limit switch
Damper
Forecast of cause
Limit switch failure
Shorted connector/wire
Damper faulure
Controller PCB failure
Check point 1. Check limit switch
•
Check operation of limit switch. (any blocking by dust, etc.)
•
Remove limit switch and check ON/OFF switching operation by using a meter.
-> If limit switch is detective, replace it.
↓
Check point 2. Check connector (CN18)/wire
Check loose contact of CN18/shorted wire (pinched wire).
-> Replace limit switch if the wire is abnormal
↓
Check point 3. Check Damper
•
Check the obstruction of damper movement.
•
Check the damper movement.
-> Replace damper if the damper is abnormal
↓
Check point 4. Replace the main PCB
If Check Point 1 and 3 do not improve the symptom, replace the main PCB.
↓
End
2-20. E: 57. Damper (Open/Close) detection limit switch error
- (03-33) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AGHG09KVCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 15 SR_CH01_MU001EG_04 ...
Page 40: ...2 6 Outdoor unit 01 34 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 41: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 15 SR_CH02_MU001EG_05 ...
Page 44: ......
Page 161: ...3 TROUBLESHOOTING 2022 04 13 SR_CH03_MU001EG_04 ...
Page 164: ......
Page 259: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU001EG_06 ...
Page 262: ......
Page 351: ...5 FILED WORKING 2022 04 13 SR_CH05_MU001EG_05 ...