-32-
4.9. Checking and Setting of Piping Specifications/Detector
4.9.1. Checking piping parameter
4.9.1.1. 1-path/energy measurement mode and 2-path mode
Key operation
Description
Display
0.000 m/s
0.000 m3/h
▼
Press the
key for 3 times to display “MEASURE SETUP”.
MEASURE SETUP
ENT
▼
Press the
ENT
key once to display “MEASUREMENT MODE”.
MEASUREMENT MODE
1 PATH
▼
Press the
key for 7 times to display “PROCESS SETTING”.
PROCESS SETTING
S= 16( 48mm)
ENT
▼
Press the
ENT
key once to display “OUTER DIAMETER”.
OUTER DIAMETER
60.00 mm
▼
Press the
key once to display “PIPE MATERIAL”.
PIPE MATERIAL
PVC
▼
Press the
key once to display “WALL THICKNESS”.
WALL THICKNESS
4.00 mm
▼
Press the
key once to display “LINING MATERIAL”.
LINING MATERIAL
NO LINING
▼
Press the
key once to display “KIND OF FLUID”.
KIND OF FLUID
WATER
▼
Press the
key once to display “VISCOSITY”.
VISCOSITY
1.003800 E-6m2/s
▼
Press the
key once to display “SENSOR MOUNT”.
SENSOR MOUNT
V METHOD
▼
Press the
key once to display “SENSOR TYPE”.
SENSOR TYPE
FSSA/FSSG
ESC
Press the
ESC
key twice, and the
key twice to return to the
measurement mode.
0.000 m/s
0.000 m3/h