-7-
3. INSTALLATION
Select an installation location that satisfies the following conditions for ease of maintenance and inspection, service life of
the instrument, and assurance of reliability all considered.
(1) A place where ambient temperature and humidity are -20 to +55°C and 95% RH or less for flow transmitter
(FSV)
(2) A place not exposed to direct sunshine nor inclement weather.
(3) Space for periodic inspection and wiring work is available.
(4) A place not subjected to radiated heat from a heating furnace, etc.
(5) A place not subjected to corrosive atmosphere.
(6) A place not to be submerged.
(7) A place free from excessive vibration, dust, dirt, and moisture.
3.1. Installation location of flow transmitter
Secure at least 100 mm of space between the flow transmitter and nearby wall. Also secure a space of opening the front
cover in case of maintenance.
Allow space for cable wiring under the case.
OP
E
N
244mm
100mm
or
more
245mm
348mm
Fig. 3.1 Top view of mounting
CAUTION