-109-
6.5. Error and remedy
6.5.1. Display error
State Probable
cause
Nothing is displayed.
Power supply is not turned on.
Low power supply voltage
Fuse is blown out.
LCD error
Refer to “6.5.8. Remedying a hardware fault”.
Reverse polarity of DC power supply
Upper side appears black.
Low power supply voltage
Reverse polarity of DC power supply
LCD error
Refer to “6.5.8. Remedying a hardware fault”.
Irrational display
Hardware error
Refer to “6.5.8. Remedying a hardware fault”.
Pale display
Ambient temperature is low (-20
C or lower)
Increase temperature.
LCD has reached the end of its service life.
Replace the LCD.
Entire display is blackish.
Ambient temperature is high (50
C or higher)
Decrease temperature.
LCD characters are skipped.
LED does not come on
Refer to “6.5.1.1. Checking the LCD/LED” for LCD/LED.
The dots on the LCD are missing or the LED does not come on.
Refer to “6.5.8. Remedying a hardware fault”.
LED is displayed in red.
(ST1 or ST2)
Received wave is abnormal.
Refer to “6.5.1.2. Checking the LED lit in red (1)”.
LED is displayed in red.
(ST2)
Temperature is abnormal.
Refer to “6.5.1.2. Checking the LED lit in red (2)”.
6.5.1.1. Checking the LCD/LED
Follow the procedure shown below to check possible display errors.
Key operation
Description
Display
▼
Press the
key for 4 times to display “MAINTENANCE MODE”.
MAINTENANCE MODE
ENT
▼
Press the
ENT
key once to display “RAS INFORMATION”.
RAS INFORMATION
0000000000000000
▼
Press the
key for 16 times (14 times for 2-pipe mode) to display
“LCD/LED CHECK”.
LCD/LED CHECK
ENT
▼
Press the
ENT
key once.
Lit in red
▼
Every time the
key is pressed, the display is switched in the order
shown below.
LCD: OFF completely LED: Lit in green
LCD: Darkened
LED: Lit in red
If dots on the LCD are missing or the LED does not come on, the
LCD/LED may have failed.
Lit in green
ESC
Obtain a measurement-mode display using the
ESC
key and the
key.
0.000 m/s
0.000 m3/h