155
EN-US
Finally...
General
-
Isolate the inverter in its unloaded state from the AC grid and the DC power supply (set
DC disconnector to level 0).
-
Refit and attach all removed Datcom lines (restore inverter to original state prior to the
repair or safety inspection).
-
If necessary, reinstall the AC lead in the PG screw joint.
-
Check whether conductive objects are deposited in the housing.
-
Mount Datcom lid with 4 screws 5x16 TX25 –
2 Nm
Visual Inspection
Deficiencies identified that may be the cause of other hazards must be repaired immedi-
ately, otherwise further use must be restricted until the defect is rectified.
-
Missing or damaged housing parts, insulating parts, or protective covers.
-
Soiling and blockage of cooling vents.
-
Check that safety labels are present (such as warning notices, grounding symbols, rat-
ing plates) and replace, supplement, or correct if necessary.
-
Ensure that all safety-related labels or symbols, rated values and position indicators
are legible.
Summary of Contents for Primo 208-240
Page 2: ...2...
Page 5: ...Allgemeine Informationen...
Page 6: ......
Page 14: ...14...
Page 15: ...Fehler Suchhilfe...
Page 16: ......
Page 34: ...34...
Page 35: ...Komponenten austauschen...
Page 36: ......
Page 55: ...55 DE DC Trenner auf ON stellen 6...
Page 66: ...66...
Page 67: ...Sicherheitstechnische berpr fung...
Page 68: ......
Page 80: ...80...
Page 83: ...General Information...
Page 84: ......
Page 92: ...92...
Page 93: ...Troubleshooting guide...
Page 94: ......
Page 112: ...112...
Page 113: ...Replacing components...
Page 114: ......
Page 133: ...133 EN US Set the DC disconnector to ON 6...
Page 144: ...144...
Page 145: ...Safety inspection...
Page 146: ......
Page 158: ...158...
Page 159: ...Appendix...
Page 162: ...162...
Page 163: ...163...