Contact Current
-
Measurement should only be carried out once measurement of ground conductor cur-
rent has been carried out successfully
-
The device must remain in operation.
Measurements are taken between a grounded point and the touchable, conductive part
which is not connected with the ground conductor.
The contact current must not exceed 0.5 mA *).
1 Measuring instrument
2 Inverter
6.2 Touchable, conductive part not connected to the
ground conductor
8 Insulated assembly of the object being tested
9 Measurement lead
Ri 1–2 k
Touchable, conductive parts not connected to the
ground conductor
*) These requirements relate to DIN VDE 0701-0702 and ÖVE/ÖNORM E8701-1. In addi-
tion, individual national requirements and standards must also be observed.
PE
mA
L1
1
2
9
N
PE
L1
N
9
8
6.2
Ri
1-2k
Ω
Summary of Contents for Primo 208-240
Page 2: ...2...
Page 5: ...Allgemeine Informationen...
Page 6: ......
Page 14: ...14...
Page 15: ...Fehler Suchhilfe...
Page 16: ......
Page 34: ...34...
Page 35: ...Komponenten austauschen...
Page 36: ......
Page 55: ...55 DE DC Trenner auf ON stellen 6...
Page 66: ...66...
Page 67: ...Sicherheitstechnische berpr fung...
Page 68: ......
Page 80: ...80...
Page 83: ...General Information...
Page 84: ......
Page 92: ...92...
Page 93: ...Troubleshooting guide...
Page 94: ......
Page 112: ...112...
Page 113: ...Replacing components...
Page 114: ......
Page 133: ...133 EN US Set the DC disconnector to ON 6...
Page 144: ...144...
Page 145: ...Safety inspection...
Page 146: ......
Page 158: ...158...
Page 159: ...Appendix...
Page 162: ...162...
Page 163: ...163...