The breakaway PC board of the new
RECERBO must also be removed and
returned with the faulty RECERBO to
Fronius.
Insert the previously separated brea-
kaway PC board (4) on the internal
side of the new RECERBO.
Mount the RECERBO holder (3) on the
new RECERBO
- thread the wire up
- press down.
Insert the new RECERBO assembly
The locks (2) on the RECERBO holder
must be fully engaged in the housing
frame
Insert the external fan cable in the cab-
ling (1)
Insert the Datamanager card, close the
inverter and insert into the wall bracket
(see "Replacing the Datamanager
Card" and "Opening and Closing De-
vice" sections)
(4)
(3)
NOTE!
If the breakaway PC board
is forgotten or not inserted correct-
ly, the inverter will show a status
code (482) on the display.
NOTE!
All guide pins and bolts
must be engaged.
1
2
3
(1)
(2)
(2)
4
5
6
7
Summary of Contents for Primo 208-240
Page 2: ...2...
Page 5: ...Allgemeine Informationen...
Page 6: ......
Page 14: ...14...
Page 15: ...Fehler Suchhilfe...
Page 16: ......
Page 34: ...34...
Page 35: ...Komponenten austauschen...
Page 36: ......
Page 55: ...55 DE DC Trenner auf ON stellen 6...
Page 66: ...66...
Page 67: ...Sicherheitstechnische berpr fung...
Page 68: ......
Page 80: ...80...
Page 83: ...General Information...
Page 84: ......
Page 92: ...92...
Page 93: ...Troubleshooting guide...
Page 94: ......
Page 112: ...112...
Page 113: ...Replacing components...
Page 114: ......
Page 133: ...133 EN US Set the DC disconnector to ON 6...
Page 144: ...144...
Page 145: ...Safety inspection...
Page 146: ......
Page 158: ...158...
Page 159: ...Appendix...
Page 162: ...162...
Page 163: ...163...