Fronius Primo 208-240 Service Manual & Spare Parts List Download Page 1

/ Perfect Charging / Perfect Welding / 

Solar Energy

42,0410,2172

005-08082018

Fronius Primo 208-240:
3.8-1 / 5.0-1 / 6.0-1
7.6-1 / 8.2-1

Serviceanleitung
Ersatzteilliste

Netzgekoppelter Wechselrichter

Service manual
Spare parts list

Inverter for grid-connected photo-
voltaic systems

DE

EN-US

Summary of Contents for Primo 208-240

Page 1: ...Energy 42 0410 2172 005 08082018 Fronius Primo 208 240 3 8 1 5 0 1 6 0 1 7 6 1 8 2 1 Serviceanleitung Ersatzteilliste Netzgekoppelter Wechselrichter Service manual Spare parts list Inverter for grid c...

Page 2: ...2...

Page 3: ...Grid Features 12 FCC RSS Compliance 12 Erdschluss Erkennung Unterbrechung Isolations berwachung 12 Lichtbogen Erkennung Unterbrechung 13 Software Update 13 Fehler Suchhilfe 15 Service Codes 17 Sicherh...

Page 4: ...T tigkeiten 64 Sonstige Komponenten tauschen 65 Sonstige Komponenten tauschen 65 Sicherheitstechnische berpr fung 67 Sicherheitstechnische berpr fung 69 Sicherheitstechnische berpr fung 69 Verantwortl...

Page 5: ...Allgemeine Informationen...

Page 6: ......

Page 7: ...WARNUNG Fehlerhaft durchgef hrte Arbeiten k nnen schwerwiegende Perso nen und Sachsch den verursachen Alle in der Serviceanleitung beschriebenen T tigkeiten d rfen nur von Fronius geschultem Servicepe...

Page 8: ...itstechnische berpr fung des in dieser Servicean leitung beschriebenen Ger ts Bitte beachten Sie die entsprechenden Anforderungen und Normen Ihres Landes ggf kann es zu Abweichungen der Messwerte oder...

Page 9: ...aubendreher 3 mm Steckschl ssel Steckschl ssel Einsatz SW 7 mm Steckschl ssel Einsatz SW 36 mm Steckschl ssel Einsatz SW 41 mm Gabelschl ssel SW 7 mm Gabelschl ssel SW 36 mm Gabelschl ssel SW 41 mm Se...

Page 10: ...hung von Inselverh ltnissen Der Betrieb des Wechselrichters erfolgt vollautomatisch Sobald nach Sonnenaufgang ge nug Energie von den Solarmodulen zur Verf gung steht beginnt der Wechselrichter mit der...

Page 11: ...sigen Betriebsbereich betrieben werden Alle vom Solarmodul Hersteller empfohlenen Ma nahmen zur dauerhaften Erhaltung der Solarmodul Eigenschaften ber cksichtigen Bestimmungen des Energieversorgungs U...

Page 12: ...in einer bestimmten Installation nicht auftreten Wenn dieses Ger t St rungen des Radio oder Fernsehempfanges verursacht die durch Aus und Einschalten des Ger ts festgestellt werden k nnen wird dem Be...

Page 13: ...ieb wird unterbrochen Am Display wird eine Statusmeldung State Code aus gegeben Die Statusmeldung am Display muss manuell zur ckgesetzt werden bevor der Netz Einspeisebetrieb wieder aufgenommen werden...

Page 14: ...14...

Page 15: ...Fehler Suchhilfe...

Page 16: ......

Page 17: ...Reset durchf hren Wechselrichter im lastfreien Zustand von der AC Versorgung trennen und erneut zuschalten Netzspannungs Toleranz abh ngig vom L nder Setup Service Codes Klasse 1 Statusmeldungen der K...

Page 18: ...n 3 Wiederverbindungs Limit er reicht 3 Normale gesetzliche Anfor derung kein Fehler 50 05Hz 4 Rundsteuersignale 4 Meldung an TSI Spezialis ten 5 Messfehler am Filterprint 5 Filterprint tauschen 106 N...

Page 19: ...AFCI Selbsttest Fehler 1 Selbsttest laufend Fehler haft w hrend der Fehlererken nung 1 Wechselrichter neu starten oder Software Update 2 Filterprint tauschen 247 AFCI Stromsensor Fehler 1 Datenabglei...

Page 20: ...iedrig f r Einspeisung 3 Mehr Strahlungsintensit t abwarten oder PV Module pr fen 4 Umkehrspannung des PV Generators 4 Polarit t des PV Generators umkehren 5 Betriebsart DC Festspan nung falsche Spann...

Page 21: ...steil defekt 2 AC Print tauschen 412 Eingestellte Fixspannung au erhalb des zul ssigen MPP Bereichs 1 Fixspannung zu hoch oder zu niedrig eingestellt 1 Anpassungen im Service Men pr fen 415 Freigabesi...

Page 22: ...tungsteil defekt 2 AC Print tauschen 3 Recerbo defekt 3 Recerbo tauschen 437 Problem bei der internen Fehlerbehandlung 1 Leistungsteil konnte nicht mit dem Recerbo kommunizie ren 1 Wechselrichter neu...

Page 23: ...uschen 453 Redundante Netz berwa chung hat eine fehlerhafte Netzspannung festgestellt 1 Messfehler 1 Software Update 2 Netzproblem 2 Automatisch korrigiert 3 Defekter AC Guard auf Fil terprint 3 Filte...

Page 24: ...1 Falsche Einstellung 1 ISO GFDI Einstellung pr fen 2 Erdungsfehler PV Genera tor 2 PV Generator pr fen 3 Messkreis am Leistungsteil defekt 3 DC Print und anschlie end wenn n tig AC Print tauschen 476...

Page 25: ...Schneebedeckt oder sehr verschmutzte Module 1 Module reinigen oder Schnee entfernen 2 F r Netz Einspeisebetrieb von den Modulen 2 Andere Service Codes pr fen 515 EEPROM Kommunikation fehlgeschlagen 1...

Page 26: ...Print und anschlie end wenn n tig AC Print tauschen 523 DC LOW Ch2 1 DC Hauptschalter ge ffnet 1 DC Hauptschalter schlie en 2 PV Generator nicht verbun den 2 PV Generator verbinden 3 DC Spannung f r E...

Page 27: ...ei DC2 1 DC Print tauschen 2 Defekter Stromkreis am Leistungsteil 2 AC Print tauschen 607 Fehlermeldung der RCMU mehr als 4mal in 24 Stun den 1 Erdungsproblem 1 Nach 24 Stunden automa tisch korrigiert...

Page 28: ...ten 734 Update Datei nicht erkannt 1 Update Datei hat falsches Format 1 Update Datei richtig benen nen z B Froxxxxx upd 2 Update in der falschen Datei 2 Update im Hauptverzeichnis speichern 735 F r de...

Page 29: ...einiger Prints sind inkompatibel 3 Wechselrichter tauschen 751 Echtzeit Uhr verloren 1 Wechselrichter hatte mehr als 5 Tage lang keine AC Ver bindung 1 Zeit einstellen 2 Speicher am Recerbo defekt 2 R...

Page 30: ...u laden 2 Defekter Recerbo 2 Recerbo tauschen 775 Falsche Programmierung des Leistungsteils 1 Leistungsteil oder Filterprint nicht programmiert 1 Siehe Ger t Info Men Nach fehlenden Versionsinfos such...

Page 31: ...chung zwischen Wechselrichter Abweichung des kWh Werts zwischen den Wechselrichtern Abh ngig von den Einstellun gen im Fronius Solar web Einstellungen in der System verwaltung in Fronius So lar web pr...

Page 32: ...stallierten Wechselrichter Am Display angezeigter Service Code State PS Men Name der PV Anlage Name des Anlagenbetreibers Betriebsdauer der Anlage Standort der Anlage Anzahl der Installierten Wechselr...

Page 33: ...XV 6HUYLFH RGH LVWH HLJHQ DQGHUH HUlWH DXFK GHQ HKOHU 1 1 3U IH 1HW 3U IH 0HQ 727 5 3U IH UURU RXQWHU 5 3U IH 1HW SDUDPHWHU 5 URQLXV 7HFK6XSSRUW NRQWDNWLHUHQ URQLXV 7HFK6XSSRUW NRQWDNWLHUHQ YHQWORJJLQ...

Page 34: ...34...

Page 35: ...Komponenten austauschen...

Page 36: ......

Page 37: ...e und der Durchf h rung von Service und Reparaturt tigkeiten unbedingt das Kapitel Sicherheits vorschriften lesen WARNUNG Ein elektrischer Schlag kann t dlich sein Gefahr durch Netzspan nung und DC Sp...

Page 38: ...tauschen Innenl fter tauschen Datamanager Card tauschen Display Print RECERBO tauschen Filter Print PrimoFIL tauschen Leistungs Print PrimoPS tauschen Sonstige Komponenten tauschen WARNUNG Gefahr eine...

Page 39: ...er t vom Netz trennen ein verst ndliches Warnschild gegen Wiedereinschalten anbringen mit Hilfe eines geeigneten Messger tes sicherstellen dass elektrisch gela dene Bauteile z B Kondensatoren entladen...

Page 40: ...G Der ffnungswinkel darf 11 nicht bersteigen Wechselrichter im Anschlussbereich aus der Wandhalterung nach vorne wegziehen anschlie end Wechsel richter anheben und nach oben ent nehmen Geh use ffnen 4...

Page 41: ...kel nach unten ziehen a und unter Zug auf die Grundschale aufschwenken b WICHTIG Beim Schlie en des Deckels darauf achten dass die Tastenfedern in die F hrungen einrasten Den Leistungsteildeckel 3 ans...

Page 42: ...vorhanden Datenkommunika tions Leitungen wieder mit dem Wech selrichter verbinden Wechselrichter mit 2x Schrauben 5x25 mm TX25 4 in der Wandhalterung fi xieren Anzugsmoment 2 5 Nm DATCOM Deckel 6 anse...

Page 43: ...ung l sen und aus Wandhalterung entnehmen DC und AC Kabel am Klemmblock abschlie en DC Trenner tau schen DC Trenner ausbauen Halteclip 1 nach vorne entfernen Schaltknopf mit Welle 2 nach unten entfern...

Page 44: ...renner einbauen Trenner in Wandhalterung einsetzen und mit 4x Schraube 4x9 mm TX20 3 fixieren Anzugsmoment 2 Nm WICHTIG Beim Einsetzen des Schalt knopfes mit Welle auf die Ausnehmungen achten Schaltkn...

Page 45: ...oment 1 5 1 8 Nm Nicht ben tigte oder freie Erdungsklemmen am DC Trenner TX 20 ebenfalls mit 1 6 Nm anziehen Ger t in die Wandhalterung einsetzen und verschrauben Gegebenenfalls Datenkommunikations Le...

Page 46: ...gsteildeckel entfernen Au enl fter tau schen Rechten Au enl fter tauschen Molexstecker 2 abstecken Kabel aus den Klemmnasen l sen und ausf deln Wechselrichter vorsichtig umdrehen sodass die R ckseite...

Page 47: ...ehen Den rechten Au enl fter von der L f terhalterung entfernen die beiden Verriegelungen 7 nach au en dr cken Beim neuen L fter die Entfernung x zwischen Dichtungspfropfen und L f ter vorsichtig auf...

Page 48: ...etzen L fter oben ansetzen und nach unten dr cken L fterkabel einf deln Dichtungspfropfen 6 einsetzen WICHTIG Die Dichtheit des Dichtungs pfropfens muss gegeben sein L fterhalterung 5 wieder aufsetzen...

Page 49: ...Au enl fter tauschen Molexstecker 1 abstecken Kabel aus den Klemmnasen l sen und ausf deln Wechselrichter vorsichtig umdrehen sodass die R ckseite zug nglich ist 2x Schraube 5x14 mm TX25 3 entfer nen...

Page 50: ...TIG Beim Einsetzen des neuen L f ters die Luftstromrichtung beachten Der L fter muss zur Ger temitte blasen Neuen Au enl fter in die L fterhalte rung einsetzen L fter oben ansetzen und nach unten dr c...

Page 51: ...n fixieren Abschlie ende T tigkeiten Dichtheit der Durchf hrungspfropfen berpr fen Leistungsteildeckel montieren Ger t in die Wandhalterung einsetzen und verschrauben Gegebenenfalls Datenkommunikation...

Page 52: ...ter tau schen Innenl fter ausbauen Molexstecker 1 abstecken Innenl fter demontieren Kunststoff Spreizbolzen mittels Schraubendreher aus der Niete dr cken anschlie end L fter von der Niete ziehen Innen...

Page 53: ...T tigkeiten Leistungsteildeckel montieren Ger t in die Wandhalterung einsetzen und verschrauben Gegebenenfalls Datenkommunikations Leitungen anschlie en DATCOM Deckel montieren AC Versorgung wiederher...

Page 54: ...Card vom Print RECERBO abstecken und entnehmen Datamanager Card einbauen Neue Datamanager Card am Print RECERBO anstecken Datamanager Card mit 1 x Schraube TX20 3 fixieren 4 x 8 mm Datamanager Card 4...

Page 55: ...55 DE DC Trenner auf ON stellen 6...

Page 56: ...aus der Kabelf h rung 1 nehmen Verriegelungen 2 der RECERBO Halterung nach oben dr cken RECERBO Baugruppe entnehmen Halterung 3 vom RECERBO abneh men Abbrech Print 4 vom defekten RECERBO abbrechen RE...

Page 57: ...rriegelungen 2 der RECERBO Halterung m ssen vollst ndig in der Geh useschale eingerastet sein Aussenl fter Kabel in die Kabelf h rung 1 einlegen Datamanager Card einbauen Wech selrichter schlie en und...

Page 58: ...abgesteckt wurden Buchsenleisten entfernen Falls vorhanden Optionskarten z B Datamanager Card entfernen Print RECERBO entnehmen Filter Print Primo FIL tauschen PrimoFIL ausbauen Kabelverbindungen 1 4...

Page 59: ...ckkarten 10 wieder in Geh use Grundschale einh ngen Erdungslasche 11 zur ck biegen Printhalterung 8 wieder einschieben Ferritkerne 5 und 7 wieder im Trennblech fixieren Alle Kabelverbindungen 1 bis 7...

Page 60: ...ndhalterung einsetzen und verschrauben Gegebenenfalls Datenkommunikations Leitungen anschlie en DATCOM Deckel montieren AC Versorgung wiederherstellen DC Trenner auf ON stellen Nach Inbetriebnahme des...

Page 61: ...erung l sen und aus Wandhalterung entnehmen Leistungsteildeckel entfernen Leistungs Print PrimoPS tau schen PrimoPS ausbauen Luftf hrung 1 abnehmen Alle Kabel 2 4 am PrimoPS abste cken 14x Schraube 4x...

Page 62: ...oder sonst irgendwie besch digen K hlk rper reinigen a K hlk rper mit W rmeleitmedium R ckst nden b sauberer K hlk rper PrimoPS einbauen Die 2x Blisterverpackungen 8 von den Modulen des neuen Leistun...

Page 63: ...lk rper verschrauben Anzugsmoment 0 5 Nm 4x Schraube 4 x 9 mm TX20 6 mit 2 0 Nm nachziehen Print Primo PS mit 14x Schraube 4x9 mm TX20 5 verschrauben Anzugsmoment 2 Nm Alle Kabel 2 4 wieder am PrimoPS...

Page 64: ...gkeiten Leistungsteildeckel montieren Ger t in die Wandhalterung einsetzen und verschrauben Gegebenenfalls Datenkommunikations Leitungen anschlie en DATCOM Deckel montieren AC Versorgung wiederherstel...

Page 65: ...scht werden Geh useteile ausgenommen Deckel Induktivit ten K hlk rper Dichtungen ausgenommen die Dichtung an den Deckeln Die Deckel DATCOM Deckel und Leistungsteil Deckel k nnen als Baugruppe mit aufg...

Page 66: ...66...

Page 67: ...Sicherheitstechnische berpr fung...

Page 68: ......

Page 69: ...Pr fung begonnen wird Kann eine der Pr fungen nicht durchgef hrt werden so ist vom Pr fer zu entscheiden und es obliegt seiner Verantwortung und Haftung ob die Sicherheit des Ger tes trotzdem best ti...

Page 70: ...hmen treffen die das Auftreten von gef hrli chen Ber hrungsspannungen vermeiden Der Messbereich muss mindestens die Werte von 0 25 mA bis 19 mA umfassen Die Pr feinrichtung muss den gemessenen Strom u...

Page 71: ...chutzabdeckungen d rfen nicht fehlen oder besch digt sein Unzul ssige nderungen d rfen nicht vorhanden sein z B Ein Umbauten welche nicht vom Hersteller frei gegeben sind K hl ffnungen d rfen nicht ve...

Page 72: ...lag kann t dlich sein Bei der Isolationswider stands Pr fung wird zum Teil mit Hochspannung gemessen Vor Beginn der Pr fung muss das Verfahren vollst ndig verstanden werden Die folgenden Sicherheitsma...

Page 73: ...zleiter Funktion des Wechselrichters gegeben ist Auf eine sichere Trennung des zu pr fenden Ger tes vom AC Netz ist zu achten Netzleitung L N darf nicht angeschlossen sein Sollte das AC Netz nicht von...

Page 74: ...bestehen z B Datenleitungen Montage Leitf hige Gegenst nde aus dem Geh use entfernen Fehlende Geh useteile montieren Nachdem der Wechselrichter angeschlossen wurde diesen wieder in Betrieb nehmen F r...

Page 75: ...Schutzleiter Stroms mit Stromzange ber PE Leiter 1 Messeinrichtung 2 Wechselrichter 8 Isolierte Aufstellung des Pr flings 9 Messleitung Beispiele f r die Messung des Schutzleiter Stroms Differenzstro...

Page 76: ...hrbaren leitf higen nicht mit dem Schutzleiter verbundenen Teil Der Ber hrstrom darf 0 5 mA nicht bersteigen 1 Messeinrichtung 2 Wechselrichter 6 2 Ber hrbarer leitf higer nicht mit dem Schutzleiter...

Page 77: ...chraube 5x16 TX25 montieren 2 Nm Sichtpr fung Erkennbare M ngel die Anlass anderer Gef hrdungen sein k nne m ssen eine sofortige Instandsetzung oder Einschr nkung der weiteren Verwendung bis zur M nge...

Page 78: ...ptschalter und DC Hauptschalter Lastfrei oder bei minimaler Last durchf hren jedoch nicht im Standby Modus DC Hauptschalter ausschalten Wechselrichter muss auf St rung gehen und die Einspeisung unterb...

Page 79: ...h die verwendeten Pr fmittel und Kalibrierdaten angeben Kann eine Einzelpr fung nicht durchgef hrt werden ist diese Entscheidung vom Pr fer zu begr nden und zu dokumentieren Gilt die Pr fung als nicht...

Page 80: ...80...

Page 81: ...nced Grid Features 90 FCC RSS Compliance 90 Ground Fault Detector Interrupter Insulation Monitoring 90 Arc detection interruption 90 Software Update 91 Troubleshooting guide 93 Service codes 95 Safety...

Page 82: ...rimoPS power PC board 139 Final Tasks 142 Replacing other components 143 Replacing other components 143 Safety inspection 145 Safety inspection 147 Safety Inspection 147 Responsibility 147 Scope of Ap...

Page 83: ...General Information...

Page 84: ......

Page 85: ...tem WARNING Work performed incorrectly can cause serious injury and damage All activities described in the service manual must only be carried out by a trained Fronius service technician Please note t...

Page 86: ...ice described in this service man ual Please observe the requirements and standards for your particular country since there may be deviations in the measured values or inspection steps If there are no...

Page 87: ...mm slotted screwdriver Socket wrench Wrench socket size 7 mm Wrench socket size 36 mm Wrench socket size 41 mm Flat spanner size 7 mm Flat spanner size 36 mm Flat spanner size 41 mm Diagonal cutting p...

Page 88: ...nitoring grid voltage and frequency As soon as there is a sufficient level of irradiance the solar inverter starts feeding energy into the grid The inverter ensures that the maximum possible power out...

Page 89: ...result in serious injury and damage Text of Warning Notices WARNING Danger of electric shock Non Isolated Inverter Do not remove cover No user serviceable parts inside Refer servicing to qualified ser...

Page 90: ...not cause harmful interference 2 The device must accept any interference received including interference that may cause undesired operation Ground Fault De tector Interrupt er Insulation Monitoring Th...

Page 91: ...from there to the in verter and the update process is started by going to the SETUP menu and selecting USB The update file must be located in the root directory of the USB stick NOTE This product is e...

Page 92: ...92...

Page 93: ...Troubleshooting guide...

Page 94: ......

Page 95: ...voltage tolerance depends on the country setup Class 1 service codes Status codes in class 1 are typically temporary Their cause lies in the grid The inverter s initial response is to disconnect from...

Page 96: ...ment error on filter PC board 5 Replace filter PC board 106 Grid frequency below per missible limits 1 Grid frequency error 1 Check grid frequency 2 Incorrect values in service menu incorrect setup 2...

Page 97: ...inued Check PV generator 245 AFCI self test error 1 Self test running defective during fault detection 1 Restart inverter or update software 2 Replace filter PC board 247 AFCI current sensor fault 1 D...

Page 98: ...infeed 3 Wait for more radiation in tensity or check solar modules 4 Reverse voltage of PV gen erator 4 Reverse polarity of PV gen erator 5 DC operating mode fixed voltage incorrect voltage 5 Check M...

Page 99: ...ting current grid 2 Power module faulty 2 Replace AC PC board 412 Set fixed voltage outside of permissible MPP range 1 Fixed voltage set too high or too low 1 Check adjustments in ser vice menu 415 Re...

Page 100: ...module could not communicate with Recerbo 1 Restart inverter or update software 2 Power module faulty 2 Replace AC PC board 3 Recerbo faulty 3 Replace Recerbo 438 Problem when transmitting error 1 Pow...

Page 101: ...wer module 4 Replace AC PC board 454 Redundant grid monitoring has detected faulty grid fre quency 1 Measurement error 1 Software update 2 Grid problem 2 Automatically corrected 3 Faulty AC guard on f...

Page 102: ...too low 2 Grid failure 3 Missing internal power sup ply 3 Replace AC PC board 4 Missing internal power sup ply 4 Replace filter PC board 480 Power module and display software incompatible 1 Old power...

Page 103: ...y 2 Replace power module 517 Power module derating caused by excessive tem perature 1 Ventilation opening blocked 1 Clean ventilation openings 2 Ambient temperature too high 2 Change setup location 3...

Page 104: ...e 1 Old software 1 Software update 2 Old software 2 Reload setup 3 Incompatible hardware com bination 3 Check hardware compo nents 559 Recerbo function not sup ported 1 Old software 1 Software update...

Page 105: ...ivation 1 Occurs once 1 Automatically corrected 2 Recerbo faulty 2 Replace Recerbo 711 EEPROM fault 1 Recerbo faulty 1 Replace Recerbo 712 Error when writing to EE PROM 1 Occurs once 1 Automatically c...

Page 106: ...ormatting 2 Format USB flash drive 738 Log file creation not possi ble 1 Incorrectly formatted USB flash drive 1 Format USB flash drive with FAT32 2 USB flash drive password protected 2 Remove passwor...

Page 107: ...ce ribbon cable 3 Recerbo faulty 3 Replace Recerbo 4 On board memory PC board faulty 4 Replace inverter 762 Read error on memory PC board 1 Integrated memory PC board missing 1 Use install original me...

Page 108: ...uring error channel 3 Current from channel 3 is dif ferent from the others Check settings DC fuses and modules 904 Measuring error channel 4 Current from channel 4 is dif ferent from the others Check...

Page 109: ...1 No response from the invert er for 24 h message to Dat alogger or Datamanager 1 Check LED status of Data manager or Datalogger 2 No response from the Fro nius sensor card for 2 h message to Datalog...

Page 110: ...nverter Service code shown on the display state PS menu Name of PV system name of system operator System duration of operation System location Number of inverters installed in the system type serial n...

Page 111: ...FKHFN JULG VRODU PRGXOHV 6HH URQLXV VHUYLFH FRGH IRU GHWDLOV LVW QYHUWHU HUURU XQOLNHO 3 ERDUG LQYHUWHU PXVW EH UHSDLUHG 6HH URQLXV VHUYLFH IRU GHWDLOV FRGH OLVW UH RWKHU GHYLFHV DOVR VKRZLQJ WKH HUUR...

Page 112: ...112...

Page 113: ...Replacing components...

Page 114: ......

Page 115: ...lt age from solar modules The connection area should only be opened by an authorized electrician The separate power stage set area should only be disconnected from the connection area after first bein...

Page 116: ...on Overview The Replacing Components chapter is divided into the following sections Opening and closing the housing Replacing the DC disconnector Replacing the external fan Replacing the internal fan...

Page 117: ...al Before opening the device Set power switch to O Disconnect the device from the grid Attach a clear warning sign advising others not to switch the power source back on Use a suitable measuring instr...

Page 118: ...l bracket then lift the inverter and remove it from above Opening the housing Loosen 4 x 5x18 mm TX25 screws 5 and the sealing washer until the power module cover 6 can be removed Close the hous ing C...

Page 119: ...base shell b IMPORTANT When closing the cover make sure that the springs on the keys en gage in the guides Then fasten the power module cover 3 with 4 x 5x18 mm TX25 screws 2 with a sealing washer Ti...

Page 120: ...lines to the inverter Fasten the inverter to the wall bracket with 2 x 5x25 mm TX25 screws 4 Tightening torque 2 5 Nm Attach the DATCOM cover 6 and fix with 2x TX25 screws 5 Tightening torque 2 5 Nm...

Page 121: ...from the wall bracket and remove Disconnect the DC and AC cables from the terminal block Replacing the DC disconnector Removing the DC Disconnector Remove the retaining clip 1 to the front Remove the...

Page 122: ...the DC Disconnector Insert the disconnector into the wall bracket and fix with 4 x 4x9 mm TX20 screws 3 Tightening torque 2 Nm IMPORTANT When inserting the shift knob with shaft pay attention to the...

Page 123: ...5 to 1 8 Nm Tighten earthing terminals that are surplus or not needed to the DC disconnector TX 20 also with a torque of 1 6 Nm Insert the device into the wall bracket and tighten screws If applicable...

Page 124: ...power module cover Replacing the ex ternal fan Replace the right external fan Disconnect the Molex plug 2 Release the cable from the clamping nose and feed it out Carefully turn the inverter round so...

Page 125: ...sealing plug 6 Remove the right external fan from the fan holder push the two locking devices 7 out wards In the new fan carefully set the distan ce x from the sealing plug to the fan to a length of...

Page 126: ...nal fan into the fan holder Position the fan at the top and push downward Feed in the fan cable Insert the sealing plug 6 IMPORTANT The sealing plug must not le ak Replace the fan holder 5 making sure...

Page 127: ...lace the left external fan Disconnect the Molex plug 1 Release the cable from the clamping nose and feed it out Carefully turn the inverter round so that the rear is accessible Remove 2 x 5x14 mm TX25...

Page 128: ...IMPORTANT When installing the new fan note the airflow direction The fan must blow towards the center of the device Insert the new external fan into the fan holder Position the fan at the top and push...

Page 129: ...to the clamping nose Final Tasks Check that the sealing plug is not leaking Attach the power module cover Insert the device into the wall bracket and tighten screws If applicable connect the data comm...

Page 130: ...acing the in ternal fan Removing the Internal Fan Disconnect the Molex plug 1 Remove the internal fan Push the plastic expansion pin out of the rivet using a screwdriver then pull the fan off the rive...

Page 131: ...s Attach the power module cover Insert the device into the wall bracket and tighten screws If applicable connect the data communication lines Attach the DATCOM cover Reconnect the AC power supply Set...

Page 132: ...move the Datama nager card from the RECERBO PC board Installing the Datamanager Card Insert the new Datamanager card into the RECERBO PC board Fix the Datamanager card with 1 x 4x8 mm TX20 screw 3 Dat...

Page 133: ...133 EN US Set the DC disconnector to ON 6...

Page 134: ...manager Card sections Remove the external fan cable from the cabling 1 Push the locks 2 on the RECERBO holder upward Remove the RECERBO assembly Remove the holder 3 from the RECERBO Remove the breaka...

Page 135: ...e new RECERBO assembly The locks 2 on the RECERBO holder must be fully engaged in the housing frame Insert the external fan cable in the cab ling 1 Insert the Datamanager card close the inverter and i...

Page 136: ...he data communication cables and terminating plugs Remove socket strips If installed remove option cards e g the Datamanager card Remove the RECERBO PC board Replacing the Pri moFIL filter PC board Re...

Page 137: ...in cards 10 out of the housing base shell Remove the PrimoFIL PC board Installing PrimoFIL On a new PrimoFIL PC board remove the protective film from the thermal pad Carefully insert the PrimoFIL PC...

Page 138: ...the female connectors are present and have not yet been connected with the rest of the data communication cables and terminating plugs Plug in female connectors Insert the external fan cable into the...

Page 139: ...ta communication lines Loosen unit from the wall bracket and remove Remove the power module cover Replacing the Pri moPS power PC board Removing PrimoPS Remove air duct 1 Remove all cables 2 4 from Pr...

Page 140: ...o not scratch it or damage it in any other way Clean the heatsink a Heatsink with heat conducting resi dues b Clean heatsink Installing PrimoPS Remove the 2 x blister packs 8 from the modules of the n...

Page 141: ...ule onto the heat sink with 4 x 4x9 mm TX20 screws 6 Tightening torque 0 5 Nm Tighten the 4x 4x9 mm TX20 screws 6 to 2 0 Nm Fix the PrimoPS PC board with 14 x 4x9 mm TX20 screws 5 Tightening torque 2...

Page 142: ...tach the power module cover Insert the device into the wall bracket and tighten screws If applicable connect the data communication lines Attach the DATCOM cover Reconnect the AC power supply Set the...

Page 143: ...ulty the entire inverter must be replaced Housing parts except lid Inductors Heat sink Seals except the seal on the lids The lids DATCOM and power module covers can be replaced as an assembly with a s...

Page 144: ...144...

Page 145: ...Safety inspection...

Page 146: ......

Page 147: ...safety of the device can still be confirmed This de cision must be justified accordingly and included in the inspection log under Notes Scope of Applica tion In principle a safety inspection must be c...

Page 148: ...The inspection facility must assess the measured current to be an effective value re gardless of the waveform Contact Current The effective inner resistance of the contact current measurement instrume...

Page 149: ...ective covers must not be missing or damaged Unauthorized modifications must not be present e g Fittings and modifications not authorized by the manufacturer Ventilation openings must not be soiled or...

Page 150: ...owing points both at the inverter as well as at the wall bracket WARNING An electric shock can be fatal Insulation resistance is measured in part using high voltage Before the test is started the proc...

Page 151: ...grid cannot be discon nected from the wall bracket the appropriate safety precautions must be taken Re insert the inverter in the wall bracket Ground to AC Ground to DC 1 Measuring instrument 2 Inver...

Page 152: ...rts Once the inverter has been connected it must be put back into operation For the mea surement the inverter must feed into the grid as failure to do this will lead to an incorrect measurement result...

Page 153: ...erential current process Measurement of the ground conductor current using injec tion probe via N and L leads As with a residual circuit breaker the currents are compared between the phase conductor L...

Page 154: ...ound conductor The contact current must not exceed 0 5 mA 1 Measuring instrument 2 Inverter 6 2 Touchable conductive part not connected to the ground conductor 8 Insulated assembly of the object being...

Page 155: ...Mount Datcom lid with 4 screws 5x16 TX25 2 Nm Visual Inspection Deficiencies identified that may be the cause of other hazards must be repaired immedi ately otherwise further use must be restricted u...

Page 156: ...main switch and DC main switch carry out with no load or minimal load but not in standby mode Switch off DC main switch Inverter must go into a fault condition and interrupt the feed in Switch off AC...

Page 157: ...ll as the inspection equipment used and calibration data must be given If an individual inspection cannot be carried out reasons for the inspector s decision are to be documented If the inspection is...

Page 158: ...158...

Page 159: ...Appendix...

Page 160: ...86 N N 8 8 8 8 KWWS ZL D UG VRODUZ HE FRP 521 86 62 5 6 67 0 021 725 1 6 1 9 5 1 62 6 0 0 0 0 0 PP URQLXV 3ULPR 0 0 0 86 5R 86 86 5R 86 86 86 86 5R 86 0 0 86 5R 86 0 5R 86 5 67 5 25 8 55 17 KWWS UHJLV...

Page 161: ...RECERBO M1 M2 M3 FAN A4 2 OPTION CARD 2 A4 1 WIRELESS LOGGER WILMA2 O GND GND ENS2 PSP_TX PSP_RX 15V DC 1 1 DC 1 2 Grafik Display Option Card Datcom STATUS LED 15V GND USB GND Sign 5V A1 DC Disconnect...

Page 162: ...162...

Page 163: ...163...

Page 164: ...d all addresses of our sales branches and partner firms Fronius International GmbH 4600 Wels Froniusplatz 1 Austria E Mail pv sales fronius com http www fronius com Fronius USA LLC Solar Electronics D...