61
WARNING!
An electrical shock can be fatal. Danger from DC
voltage from solar modules.
Inverter insulation monitoring is deactivated for grounded solar
modules.
-
Make sure that grounded solar modules are insulated
according to protection class II
-
Attach corresponding safety labels to the photovoltaic
system where they can be seen easily
-
Set the inverter so that an error message is displayed when
the fuse is triggered.
Safety
Important
Safety labels and the
fuse for solar module grounding are
not included in the inverter scope of
delivery, and must be obtained
separately.
Safety label for the solar module ground
Warnung!
Ein elektrischer Schlag kann tödlich sein.
Gefahr durch DC-Spannung von den
Solarmodulen.
Die Isolationsüberwachung des Wechsel-
richters ist deaktiviert. Die Solarmodule
sind geerdet.
Vor Arbeiten an der Photovoltaik-Anlage
AC- und DC-Seite spannungsfrei schalten.
Warnung!
Ein elektrischer Schlag kann tödlich sein.
Gefahr durch DC-Spannung von den
Solarmodulen.
Die Isolationsüberwachung des Wechsel-
richters ist deaktiviert. Die Solarmodule
sind geerdet.
Vor Arbeiten an der Photovoltaik-Anlage
AC- und DC-Seite spannungsfrei schalten.
Warnung!
Ein elektrischer Schlag kann tödlich
sein. Gefahr durch DC-Spannung von
den Solarmodulen.
Die Isolationsüberwachung des
Wechselrichters ist deaktiviert. Die
Solarmodule sind geerdet.
Vor Arbeiten an der Photovoltaik-k-
Anlage AC- und DC-Seite spannungs-
frei schalten.
Warnung!
Ein elektrischer Schlag kann tödlich
sein. Gefahr durch DC-Spannung von
den Solarmodulen.
Die Isolationsüberwachung des
Wechselrichters ist deaktiviert. Die
Solarmodule sind geerdet.
Vor Arbeiten an der Photovoltaik-k-
Anlage AC- und DC-Seite spannungs-
frei schalten.
Warnung!
Ein elektrischer Schlag kann tödlich
sein. Gefahr durch DC-Spannung von
den Solarmodulen.
Die Isolationsüberwachung des
Wechselrichters ist deaktiviert. Die
Solarmodule sind geerdet.
Vor Arbeiten an der Photovoltaik-k-
Anlage AC- und DC-Seite spannungs-
frei schalten.
Solar Module
NOTE
If the solar module manufacturer requires a ground for
solar modules at the positive pole:
-
Insert the fuse with a fuse cover in the respective fuse holder
-
Do not operate the Fronius IG Plus without fuse covers
Ground:
Inserting
Fuses
WARNING!
An electrical shock can be fatal. Danger from DC
voltage from solar modules.
Fuse covers are for installation purposes only. They offer no
protection against contact.
The DC main switch is only used to switch off power to the
power module. When the DC main switch is turned off, the
solar module ground at the negative pole remains unaffected.
Never touch the DC+ and DC-
Setting Inver-
ters for Groun-
ded Solar Mo-
dules
Inverter insulation monitoring is deactivated for grounded solar modules.
For this reason, you must make a setting in the 2nd level of the Setup
menu so that an error message is displayed when the ground fuse is
triggered. A code is required to access the 2nd level of the Setup menu.
This code can be requested from Fronius. Additional information regar-
ding accessing the 2nd level of the Setup menu will be provided along
with the code.
Summary of Contents for Fronius IG Plus 100
Page 2: ......
Page 4: ...ud_fr_st_et_01382 012008...
Page 14: ...6...
Page 15: ...7 General Information...
Page 16: ...8...
Page 20: ...12...
Page 21: ...13 Installation and Startup...
Page 22: ...14...
Page 71: ...63 Closing Fronius IG Plus Closing Froni us IG Plus 1 1 4 2 7 3 5 6...
Page 77: ...69 Operation...
Page 78: ...70...
Page 118: ...110...
Page 119: ...111 Troubleshooting and Maintenance...
Page 120: ...112...
Page 141: ...133 Appendix...
Page 142: ...134...
Page 152: ...144...
Page 155: ......