Criteria for the Proper Selection of String Fuses
Criteria for the
Proper Selec-
tion of String
Fuses
The following criteria must be fulfilled for each solar module string when
using fuse protection:
-
I
N
> 1.5 x I
SC
-
I
N
< 2.00 x I
SC
-
U
N
>/= 600 V DC
-
Fuse dimensions: Diameter 10.3 x 35 - 38 mm
I
N
Nominal current rating of fuse
I
SC
also STC, short circuit current for standard test conditions according
to solar module datasheet
U
N
Nominal voltage rating of fuse
Effects of
using underra-
ted fuses
In underrated fuses, the nominal current value is less than the short circuit
current of the solar module.
Effect:
The fuse may trip in intensive lighting conditions.
Fuse Recom-
mendations -
Application
Example
NOTE
Only select fuses suitable for a voltage of 600 V DC.
e.g.: Maximum short circuit current (I
SC
) of the solar module = 5.75 A
According to the criteria for selecting the correct fuse, the fuse must have
a nominal current greater than 1.5 times the short circuit current:
5.75 A x 1.5 = 8.625 A
The fuse that should be selected according to the ‘Fuses’ table: KLK D 9
with 9.0 A and 600 V AC / DC
General
The use of string fuses in the inverter also adds fuse protection to the
solar modules.
A crucial factor for the fuse protection of solar modules is the maximum
short circuit current (I
SC
or STC) of the respective solar module.
Summary of Contents for Fronius IG Plus 100
Page 2: ......
Page 4: ...ud_fr_st_et_01382 012008...
Page 14: ...6...
Page 15: ...7 General Information...
Page 16: ...8...
Page 20: ...12...
Page 21: ...13 Installation and Startup...
Page 22: ...14...
Page 71: ...63 Closing Fronius IG Plus Closing Froni us IG Plus 1 1 4 2 7 3 5 6...
Page 77: ...69 Operation...
Page 78: ...70...
Page 118: ...110...
Page 119: ...111 Troubleshooting and Maintenance...
Page 120: ...112...
Page 141: ...133 Appendix...
Page 142: ...134...
Page 152: ...144...
Page 155: ......