General operation
Seite/Page 204 Panel Generator Control P6+ RE0703_Kunde_eng.R06.1 - Kapitel/Chapter 11: General operation
22.3.11
11.7 Automatic adapter - optional
Fig. 11.7-1: Panel 21.02.02.009H with Automatic adapter 21.02.02.016H
Fischer Panda Art. No. 21.02.02.016H
11.7.1 Function:
The automatic adapter RE0704 extends the generator control panel P6+ with an automatic input. A potential-free
contact can be attached to this input. If this contact is closed, then the generator, which is attached to the generator
control panel P6+, is started automatically. If the contact is opened, then the generator is stopped automatically.
The automatic starting procedure consists of pre-heating (heat) and operating the starter (start). It can be again
aborted at any time by opening the contact at the automatic input.
For automatic stopping (stop) the output “Fuel pump” (clamp 9 generator control panel) is switched off. The time for
the automatic stop procedure can be terminated only by switching off generator control panel prematurely.
The times for “heat”, “start” and “stop” are separately adjustable (see below).
The additional automatic adapter switched on and off using the generator control panel with its push buttons “on”
and “off”.
If the contact at the automatic input is connected, while the generator control panel is switched on, then the automa-
tic starting procedure is carried out.
If the power supply is attached or switched on using the generator control panel, while the contact of the automatic
input is closed, then the automatic starting procedure won´t be carried out, because the generator control panel is
always switched off after attaching the power supply (generator the control panel must have been separate from the
power supply for at least 60s).
11.7.2 The mechanism entrance:
With (-) characterized connection is connected to GND.
01
02
03
01. Main terminals
02. Automatic adapter 21.02.02.016H
03. 8-pole DIP-switch