![Fischer Panda 45i pms User Manual Download Page 138](http://html1.mh-extra.com/html/fischer-panda/45i-pms/45i-pms_user-manual_2294277138.webp)
Maintenance Instructions
Seite/Page 138 - Kaptitel/Chapter 7: Maintenance Instructions
8.10.14
7.21 Replacing the V-belt at Kubota 02/05 series
NOTE:Reprehensive procedure
The described procedure is representative for Fischer Panda generators.
The original location of the item must be taken from the generator descrip-
tion of this manual. All replacements and repairs should be done by a trained
person.
Due to the relatively high ambient temperature inside the closed sound insulation capsule (approx. 85 °C), the useful
life of the V-belt is reduced. It is possible that the plasticisers in the rubber compounds may partially lose their effec-
tiveness even after a short operating time because the air in the sound insulated capsule can be both relatively
warm and dry.
The V-belt must therefore be checked at very short time intervals. It may be necessary to replace the V-belt after
several weeks because of unfavourable conditions. A replacement interval of 250 operating hours must never be
exceeded. The V-belt should be inspected after 50 operating hours. The V-belt must be considered a wearing part.
Fig. 7.21-1: Alternator fixing screw
1. Loosen the fixing screw above the alternator.
Wrench with width across flats of 12 mm.
01. Fixing screw
01
12
Summary of Contents for 45i pms
Page 3: ...8 10 14 Kapitel Chapter A Seite Page 3...
Page 4: ...Seite Page 4 Kaptitel Chapter A 8 10 14...
Page 12: ...Seite Page 12 Kaptitel Chapter 1 8 10 14...
Page 148: ...Generator Failure Seite Page 148 Kaptitel Chapter 8 Generator Failure 8 10 14...
Page 160: ...Tables Seite Page 160 Kaptitel Chapter 9 Tables 8 10 14...
Page 176: ...Inverter Panda PMGi 45 Seite Page 176 Kaptitel Chapter 10 Inverter Panda PMGi 45 8 10 14...
Page 212: ...Seite Page 212 Kapitel Chapter 6 Annex 8 10 14 Leere Seite Intentionally blank Annex...