FIKE CORPORATION
PREFACE
UL S2203
SHP Product Manual
Page 3 of 43
FM 0Z8A0.AY
Manual P/N: 06-130
Rev. No: 3, 04/02
Sequential Detection
A detection scheme where the sum total of active detectors on the initiating
circuits must be two or more before the system will enter the pre-discharge
state.
Single Detector Release
Detection
A detection scheme where activation of one detector causes the system to
enter the pre-discharge state. SDR (Single Detector Release) detector(s) are
installed on initiating circuits setup for sequential detection.
Solenoid On Time
The time (in minutes) that the solenoid is activated upon entering the release
state. Reset of the system overrides this value.
Supervisory State
(“Supervisory” Yellow LED ON, Piezo Warble) The supervisory state occurs
upon activation of a supervisory input circuit. The supervisory state is non-
latching and will follow the status of the supervisory input contact.
Trouble State
(“Trouble” Yellow LED ON, Piezo Constant) The trouble state occurs upon
any detectable condition which could impair system operation including
connection problems, ground faults, hardware problems, power problems,
configuration problems, or prematurely activated abort inputs. Certain trouble
conditions are latching; others allow the system to reset upon trouble
condition removal. Depending upon the type of trouble condition, the system
may or may not remain operational. When the system is in trouble state, it is
not in the normal state.