FIKE CORPORATION
OVERVIEW
UL S2203
SHP Product Manual
Page 7
of 43
FM 0Z8A0.AY
Manual P/N: 06-130
Rev. No: 3, 04/02
2.5
SHP FEATURES
•
General
Microprocessor-controlled
Power-limited on all circuits except
power connections (P1)
Field selection of either sprinkler
(solenoid) or suppression (ARM-III)
operation
Eight system status LEDs to provide
positive indication of system status
Seven segment diagnostic LED for
trouble and event occurrences
System configuration via dip-switches
Local piezo with distinct event tones
Reset switch
Audible silence switch
Disable Mode for audible and release
circuits
Disable switch for release circuits
Alarm and trouble resound
•
Power
Integral 2.6 amp power supply at
24VDC nominal
Selection of 120, or 240/208 VAC power
input at 50 or 60 hertz
Supplemental power input capability up
to 8 amps at 24 VDC
Resettable and non-resettable regulated
power output
Battery/Earth fault supervision
7 AH to 18 AH battery options, up to 90
hours standby
•
Enclosure
Steel enclosure 21” high by 14.35” wide
by 4” deep (Back-box dimensions)
Enclosure is equipped with a .50” wide
lip to facilitate flush mounting
Removable door for easy installation
Enclosure is available in Red or Gray
•
Initiating Device Circuits
Up to two Style B initiating device
circuits capable of sequential alarm,
cross-zone, or single detector release
operation with an overall system
capacity of 50 detectors maximum
Up to three Style B initiating device
circuits capable of monitoring closed
contact devices
Optional Class A module that converts
all four initiating device circuits to Style
D wiring and operation
•
Notification Appliance Circuits
Three Style Y notification appliance
circuits rated at 2.0 amps each
•
Releasing Circuits
One Agent Release circuit with
maximum of 6 ARM III’s
or
One Solenoid release circuit which can
activate one 24V or two 12V solenoids
•
Relays
General Alarm and Trouble relays
Optional SRM4 module to add four
DPDT dry relay contact outputs
•
Sprinkler Monitoring Points
Waterflow input
Supervisory input
firealarmresources.com