EQUIPMENT
FIKE CORPORATION
Page 18 of 43
SHP Product Manual
UL S2203
Rev. No: 3, 04/02
Manual P/N: 06-130
FM 0Z8A0.AY
•
P4
– Relays:
TERMINAL
DESCRIPTION
WIRING
SPECIFICATION DETAILS
27 C
28 NC Alarm
29 NO
Common
Normally Closed
Normally Open
Power limited
SPDT Form C relay contact
DC operation: 5 amps @30VDC (pf=.35)
AC operation: 5 amps @250VAC (pf=.35)
30 C
31 NO Trouble
32 NC
Common
Normally Open
Normally Closed
Power limited
SPDT Form C relay contact
DC operation: 5 amps @30VDC (pf=.35)
AC operation: 5 amps @250VAC (pf=.35)
•
10-2172 Class A Input Module:
Optional module that provides the ability to wire input circuits in a
Class A (NFPA Style D) configuration. If the module is installed on the SHP, any of the circuits can
be converted back to Class B by clipping the associated resistor, R1-R4 (R1 for Input 1, R2 for Input
2, etc.). Maximum wire resistance total for the input circuits remain the same as listed in P2, Inputs
above.
•
10-2176 SRM4 Relay Module:
Optional module that provides four additional relay contacts (Relay 3
– Relay 6). Power limited or Class 2 output, Alarm and Trouble Relay. Each is a SPDT form C relay
contact.
Rating:
DC operation: 5 amps @30VDC (pf=.35)
AC operation: 5 amps @250VAC (pf=.35)