FIKE CORPORATION
EQUIPMENT
UL S2203
SHP Product Manual
Page 15 of 43
FM 0Z8A0.AY
Manual P/N: 06-130
Rev. No: 3, 04/02
3.6
SPECIFICATIONS
Environmental:
All electronics are rated 32
°
- 120
°
F (0
°
- 49
°
C) 85% relative humidity
Primary Input AC Power:
120 VAC, 50/60 Hertz, 1.42 Amps, 170 VA
208/240VAC, 50/60 Hertz, 0.82 Amps @ 208VAC, 0.71 Amps @ 240VAC, 170 VA
System AC line power must originate from a dedicated circuit at the main building power distribution
center. The circuit breaker shall be equipped with a lockout mechanism and be clearly labeled as a “Fire
Protection Control Circuit.”
10-2171 Controller Board:
The controller’s internal power supply provides 2.6 amps of 24VDC power. Power consumption of the
controller itself is 90ma at 24VDC in the normal standby mode.
8 “ high x 11.5” wide x 2” deep; (1.2 lbs).
•
P1
- Power Supply Input:
TERMINAL
DESCRIPTION
NOMINAL RANGE
SPECIFICATION DETAILS
1-2
24 VAC
Transformer
secondary
22-28VAC
non-power limited
3-4
BAT +
COM
Standby Battery
20.4-28VDC
non-power limited
Sealed lead-acid batteries only.
18 amp-hour maximum.
Maximum supply current: 8 amps/ 27VDC
Maximum charge current: 1.5 amps/
27VDC
4-5
COM
AUX +
Optional Auxiliary
input power supply
20-28VDC
non-power limited
Requires regulated source, UL listed for
fire protective signaling
Maximum supply current: 8 amps/24VDC
Maximum ripple: 0.100 Volts rms
NOTE:
Standby Batteries and Auxiliary Power input share the same negative (common
ground) input.
•
P2
– Input Circuits:
TERMINAL
DESCRIPTION
WIRING
SPECIFICATION DETAILS
19-20
INPUT #1
21-22
INPUT #2
Detection inputs
Power limited
Class B
(Class A with optional
10-2172 module)
4.3 K EOL resistor
Used for conventional detectors listed with
this panel (see next section) or contact
closure type detectors listed for fire alarm
use.
20
Ω
maximum wire resistance
23-24
INPUT #3
25-26
INPUT #4
Contact closure
inputs
Power limited
Class B
(Class A with optional
10-2172 module)
4.3 K EOL resistor
Used for contact closure inputs such as
Manual Release, Abort, Waterflow and
Supervisory listed for fire alarm use.
100
Ω
maximum wire resistance