FIKE CORPORATION
OPERATIONS
UL S2203
SHP Product Manual
Page 29 of 43
FM 0Z8A0.AY
Manual P/N: 06-130
Rev. No. 3, 04/02
5.0
OPERATIONS
5.1
USER SWITCH INTERACTION
The user switches provide these capabilities:
Silence Switch: Silences audibles (if currently sounding) & piezo.
Changes flashing LED’s to steady. Also used to
resound silenced outputs per below.
Reset Switch: Resets system including turning off outputs,
interrupting resettable power. Momentarily
activates piezo, all LED’s, and trouble relay.
Restores system to normal state.
SW4:
Arms or Disables the release circuits (Agent
Release and Solenoid).
5.2
DIAGNOSTIC LED CODE DESIGNATORS
The seven segment diagnostic LED cycles through display of these codes (with or with-out a period) for
the events that have occurred since the last reset. For example, if input circuit #3 is activated, the LED
displays “
3.
”.
NOTE:
The period portion of the display is often overlooked. When viewing the diagnostic codes,
do not overlook the period.
Circuit/Mode
Code
without
period
Status
Code
with
period
Status
Input # 1
1
Open
1.
Activated
Input # 2
2
Open
2.
Activated
Input # 3
3
Open
3.
Activated
Input # 4
4
Open
4.
Activated
Audible # 1
5
Open
5.
Shorted
Audible # 2
6
Open
6.
Shorted
Audible # 3
7
Open
7.
Shorted
Agent Release
Module
8
Open
8.
Shorted (or initiator open)
Solenoid
9
Open
9.
Shorted
System
0
Ground Fault
Abort Input
A
Valid Abort
Battery Failure
B
Missing Battery
2
nd
Alarm Active
C
Input Circuit # 1
C.
Input Circuit # 2
System Voltage
D
Low Voltage (<19VDC)
Microcontroller
E
Intelli-Fet lost
E.
5VDC Reference/A-D Failure
Invalid Abort
F
Abort, premature
F.
Abort, Late
Power Failure
-
AC Power Brown-Out (<85%)
-.
Auxiliary Power In (<15VDC)
5.3
SILENCING RULES
•
The Silence switch silences all activated audibles (but does not effect Relays).
•
Silenced audibles are resounded by pressing silence switch (while all audibles are silenced).
•
When manually unsilencing, local piezo is not re-annunciated
•
After silencing, entry into new states only sounds that state’s audibles (except entry into release state
resounds pre-discharge audibles plus also resounds alarm audibles in sprinkler mode).
•
Alarm, waterflow, supervisory, pre-discharge, release and trouble LED’s stay on steady after silencing
to acknowledge operator action (except upon event clear per Section 5.5).
POWER
T4
PUT
-
AUDIBLE #1
+
-
8
9
10
AUDIBLE #2
+
-
AUDIBLE #3
+
-
11
12
LIMITED
13
14
MODULE
AGENT RELEASE
+
-
SOLENOID
+
-
15
16
17
18
SILENCE
AR
M
D
IS
ABL
E
SW4
CIRCUITS
RELEASE
RESET
AC NORMAL
ALARM
PRE-DISCHARGE
RELEASE
SUPERVISORY
TROUBLE
ALARMS SILENCED
ABORT
R
DIAGNOSTIC
LED
firealarmresources.com
Summary of Contents for SHP 10-051
Page 2: ...firealarmresources com ...
Page 4: ...firealarmresources com ...
Page 48: ...firealarmresources com ...
Page 50: ...firealarmresources com ...
Page 51: ...firealarmresources com ...