SERVICING
FIKE CORPORATION
Page 36 of 43
SHP Product Manual
UL S2203
Rev. No: 3, 04/02
Manual P/N: 06-130
FM 0Z8A0.AY
0
Ground Fault
♦
Verify standoff in the center of the SHP Control
Board
does not
have the retaining nut installed
♦
Remove field wiring from terminal strips to
isolate the wire with the ground fault. When
panel clears troubleshoot wire.
A
Valid Abort
♦
Normal Operation Information
b
NOTE
: The letter “b” is often
confused with the # 6
Missing battery
♦
Verify batteries are installed properly.
♦
Verify each battery has approximately the same
voltage.
♦
Remove battery wiring harness and replace with
a 100uF 50 watt capacitor and verify charger
voltage (Reference Section 6.3.1)
C
2
nd
Alarm active on input 1 if
using 430
Ω
bases. Always
activates on first alarm if using
220
Ω
or 0
Ω
devices.
♦
Input
circuit
1
C.
2
nd
Alarm active on input 2 if
using 430
Ω
bases. Always
activates on first alarm if using
220
Ω
or 0
Ω
devices.
♦
Input Circuit 2
d
Low Voltage (<19 volts)
♦
Reference Section 5.9, Low Power Conditions
♦
Check AC and DC power input.
E
Intelli-Fet lost
♦
Reset panel, if trouble does not clear replace
SHP Control Board.
♦
E.
5V Reference/A-D Failure
♦
Reset panel, if trouble does not clear replace
SHP Control Board.
F
Abort, premature
♦
Normal Operation Information
F.
Abort, Late
♦
Normal Operation Information
-
AC Brown – out (<85%)
♦
Reference Section 6.3.1, Typical Voltages and
Tolerances
-.
Auxiliary Power Input (<15V)
♦
Check auxiliary power supply voltage (P1 Aux.
Input).