APPENDIX 1
FIKE CORPORATION
Page 38 of 43
SHP Product Manual
UL S2203
Rev. No: 3, 04/02
Manual P/N: 06-130
FM 0Z8A0.AY
SHP Battery Calculation Form
Back-up Hours required: (24, 60 or 90 hours)
Normal Operation:
Controller Current
0.090 A
Auxiliary Output Current:
_____ A
Total Normal Current =
_____ X
____hours = ____A-H
Alarm Operation:
Controller Current
0.090 A
SRM4 Current (0.100 if using SRM4, else 0.0)
_____ A
Output Device Current:
_____ A
Auxiliary Output Current:
_____ A
Total Alarm Current = _____ X
0.166 hours = ____A-H
Total A-H used =
____A-H
(X1.2 factor)
Total Power Required
____A-H
Power Supplied:
Must exceed
Controller Supplied Current:
2.6 Amps
Auxiliary In current:
______ Amps Must exceed
Total Current Supplied =
______ Amps
Total Battery Pack A-H available (7 or 18 A-H):
____A-H
SHP Battery Calculation Form
Example
Back-up Hours required: (24 or 90 hours)
Normal Operation:
Controller Current
0.090 A
Auxiliary Output Current:
0.10 A
Total Normal Current =
0.19 X
24 hours = 4.6 A-H
Alarm Operation:
Controller Current
0.090 A
SRM4 Current (0.100 if using SRM4, else 0.0)
0.10 A
Output Device Current:
1.00 A
Auxiliary Output Current:
0.10 A
Total Alarm Current = 1.29 X
0.083 hours = 0.11 A-H
Total A-H used =
4.71 A-H
(X1.2 factor)
Total Power Required
5.65 A-H
Power Supplied:
Must exceed
Controller Supplied Current:
2.60 Amps
Auxiliary In current:
0.00 Amps Must exceed
Total Current Supplied =
2.60 Amps
Total Battery Pack A-H available (7 or 18 A-H):
7.0 A-H