Technical appendix
Festo – GDCP-CAMC-G-S1-EN – 1412b – English
47
Acknowledgment contact C1, C2 [X40]
Version
Relay contact, normally open
Max. voltage
[V DC]
30 (overvoltage-proof up to 60 V DC)
Nominal current
[mA]
200 (not short-circuit proof )
Voltage drop
[V]
1
Residual current (contact
open)
[μA]
10
Switching time closing
(T_C1/C2_ON)
[ms]
(STO-A/B_OFF
+ 5 ms)
Switching time opening
(T_C1/C2_OFF)
[ms]
(STO-A/B_ON
Service life (switching cycles)
[n
op
]
10 x 10
6
(at 24 V and I
Contact
= 10 mA, the service life is
reduced with higher load currents)
1)
STO-A/B_OFF, STO-A/B_ON
è
Tab. A.10 Technical data: Electrical data of the feedback contact C1/C2
Auxiliary supply 24V, 0V [X40] – output
Version
Logic supply voltage routed out of the motor controller
(fed in at [X9], not additionally filtered or stabilised).
Reserve polarity protected, overvoltage-proof up to 60 V DC.
Nominal voltage
[V]
24
Nominal current
[mA]
100 (short circuit proof, max 300 mA)
Voltage drop
[V]
1 (for nominal current)
Tab. A.11 Technical data: Electrical data of the auxiliary supply output
Electrical isolation
Electrically isolated potential ranges
STO-A / 0V-A
STO-B / 0V-B
C1 / C2
24V / 0V (Logic supply to the motor controller)
Tab. A.12 Technical data: Electrical isolation [X40]