Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
PNU Name
Description
Options
Words Type Units Detail
49
Phase Loss Detects for various issues when the start
signal is applied
Detects for input phase loss / input phase
relationship / motor side loss
Trip On: Trips if there is an input phase loss
/ supply out of balance / motor side loss
Trip Off: The Unit will attempt to run
although the operation may be erratic.
Operating with the Trip Off for prolonged
periods may result in SCR failure
0=Trip Off,
1=Trip On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 1
50
Overheat
Detects if the internal temperature sensor
has malfunctioned
Trip On: The Unit will trip if the internal
temperature sensor malfunctions
Trip Off : The Unit will continue to operate
even if the temperature sensor has
malfunctioned.
Operating with the Trip Off for prolonged
periods may result in SCR failure
0=Trip Off,
1=Trip On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 1
51
Ph / SCR
Detects for various issues when "Starting"
or " Stopping"
Detects for input phase loss / Output phase
loss / SCR misfire
Trip On: Trips if there is an input phase loss
/ motor side phase loss / SCR misfire
Trip Off: The Unit will attempt to run
although the operation may be erratic.
Operating with the Trip Off for prolonged
periods may result in SCR failure
0=Trip Off,
1=Trip On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 1