Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
PNU
Name
Description
Options
Words Type Units Detail
16
Application
The Unit has numerous pre-set
applications built in as standard.
Select the application best suited to the
load.
The selected application will
automatically change several
parameters and functions.
Depending on the application loaded
the “
Trip Class" may also change
Refer to the separate 'applications
section' for more details
See Table 1
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 23
Default: 0
17
Trip Class
The trip class is a numeric value that
correlates the trip time with overload
level.
Select Trip class according to
application requirements
The trip time depends on the selected
"Trip Class" the duration of the
overload and the level of the over
current.
Refer to the Motor Overload 'cold' trip
curves given in the Guide.
When "Class 20" or "Class30" are
selected the Unit current rating (Unit
Amps) will be reduced to a lower value
(Rated Amps).
10=Class10,
20=Class20,
30=Class30.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 10
Max: 30
Default: 10
18
Motor
Amps
This should be set to the Full Load
Current shown on the motor plate
The overload works with multiples of
the set "Motor Amps"
Also referred to as Motor FLA
2
R/W A
Multiplier: 1
Divisor:1000
Offset: 0
Min: 0.1 x
PNU18
Max: 1 x
PNU20
Default: 1 x
PNU20
19
Reserved
--
Multiplier:
Divisor:
Offset:
Min:
Max:
Default:
Modbus RTU Parameters (continued)