![Fairford agility AGY-101 User Manual Download Page 11](http://html1.mh-extra.com/html/fairford/agility-agy-101/agility-agy-101_user-manual_538924011.webp)
10
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Horizontal Mounting
The agility
TM
unit may be mounted horizontally if required. It will be necessary to apply a deration to the
unit power in this instance
–
see Horizontal Rating Table (Page 13)
Mechanical Specification
Mechanical Specifications
Model (AGY-)
101
103
105
107
109
111
113
Frame Size
1
Heat output (W)
9
12
14
16
20
25
30
Weight kg [lb]
1.97 [4.20]
Ambient Operating Temp.
-20°C [-4°F] to 40°C [104°F] ; above 40°C
derate linearly by 2% of agility
TM
Ie per °C to
a maximum of 60°C (140°F)
Transportation and Storage
Temperature
-20°C to 60°C [-4°F to 140°F] continuous
Humidity
max 85% non-condensing, not exceeding
50% @ 40°C [104°F]
Maximum Altitude
1,000m [3281ft] ; above 1000m derate by 1%
of agility
TM
I
e
per 100m (328ft) to a maximum
altitude of 2,000m (6562ft)
Environmental Rating
Main Circuit: IP00 (IP20 with optional finger
guards); Control Circuit: IP20; No corrosive
gases permitted
Mechanical Installation (continued)