General Specification
Product Standard
EN 60947-4-2: 2012
Rated operational voltages
U
e
200Vac to 600Vac (See Key to part numbers)
Rated operational current
I
e
See Rating Table
Rating index
See Rating Table
Rated frequency/frequencies
50 - 60Hz ± 5Hz
Rated duty
Uninterrupted.
Form designation
Form 1, Internally Bypassed
Method of operation
Symmetrically controlled starter
Method of control
Semi-automatic
Method of connecting
Thyristors connected between windings and supply
Number of poles
3 main poles, 2 main poles controlled by
semiconductor switching element
Rated insulation voltage
U
i
Main circuit
See Key to
part
numbers
Control supply circuit
24Vdc
Rated impulse withstand voltage
U
imp
Main circuit
6 kV
Control supply circuit
4 kV
IP code
Main circuit
IP00 (IP20
optional)
Supply and Control circuit
IP20
Overvoltage Category / Pollution
degree
III / 3
Rated conditional short-circuit current and
type of co-ordination with associated short
circuit protective device (SCPD)
Type 1 co-ordination
See Short Circuit Protection Tables for
rated conditional short-circuit current
and required current rating and
characteristics of the associated SCPD
Electrical Installation (continued)