52
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
PNU Name
Description
Options
Words Type Units Detail
58
I Low
This can be used to detect if the motor is
running lightly loaded.
Trip On: The Unit will trip. This feature is
not active during soft start and soft stop.
Trip Off: The Unit will continue to operate
regardless of motor current
0=Trip Off,
1=Trip On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 0
59
I Limit Start Selects trip or continue if the current limit
has been active for too long
Trip On: The Unit will trip
Trip Off: The start will continue regardless
of the motor current level
0=Trip Off,
1=Trip On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 1
60
Overload
The Unit has an "Overload" function that is
an electronic equivalent to a thermal
overload.
Trip On: The Unit will trip when the
"Overload" capacity (Modbus PNU 27)
exceeds 100%
Trip Off: The Unit will continue to operate
regardless of motor current level
0=Trip Off,
1=Trip On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 1
61
Shearpin
The Shearpin is an electronic equivalent of
a mechanical Shearpin
Trip On: The Unit will trip. This feature is
not active during soft start and soft stop.
Trip Off: The Unit will continue to operate
regardless of motor current level
0=Trip Off,
1=Trip On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 1